4 Parameters
62VFD700 AC Drive Getting Started Guide
7: Optional card (By option modules)
8: User programmed
By destination and source control, user can define the reference channel freely. For example
through Menu P17, user can define the reference source. About actual application guide,
please refer to the
VFD700 Advanced User Manual
.
Parameter ID
Parameter Name
Range
【
Default
】
Change Mode
P00.05 (P08.02)
AI1 mode
0
~
6
【
6
】
Stop Only
AI1 signal can be voltage or current mode.
0: 0mA
~
20mA
1: 20mA
~
0mA
2: 4mA
~
20mA (current loosing with trip)
3: 20mA
~
4mA (current loosing with trip)
4: 4 mA
~
20mA (current loosing without trip)
5: 20mA
~
4mA (current loosing without trip)
6: 0V
~
10V
When the AI mode selection is “0
~
5”, if the input current is over 26mA, the drive will trip at
F012, the drive will stop as the mode decided by P03.10, then turn off the IGBTs.
When this parameter is set to 2 or 3, if the input current is less than 3mA, then the drive will
trip at F013, the drive will stop in the mode decided by P03.10, then turn off the IGBTs.
NOTE: If the selection is "2
~
5", once the current is less than 3mA, P08.16 (current loosing
indicator) is 1.
Parameter ID
Parameter Name
Range
【
Default
】
Change Mode
P00.06 (P04.01)
Preset1
±Max. reference
【
5.00
】
Run&Stop
Parameter ID
Parameter Name
Range
【
Default
】
Change Mode
P00.07 (P01.02)
Max. reference
0.00Hz
~
300.0Hz
【
50.00
】
Stop Only
P00.08 (P01.03)
Min. reference
0.00Hz
~
max. reference
【
0.00
】
Stop Only
If P03.01=0 (reverse is enabled), then the P00.08 is fixed at 0.00Hz.