Appendix
124VFD700 AC Drive Getting Started Guide
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P10.11
Switch
frequency auto
adjust
0: Off
1: On
1
1
Run&Stop
03F2H
P10.12
Low DC bus
operation (only
for 400V
models)
0: Off
1: On
1
0
Stop Only
03F3H
P10.13 Model code
0
~
255
1
By
model
Actual
03F4H
P10.14 Drive status
0
~
65535
1
Actual
Actual
03F5H
P10.15
Set operation
time
0
~
P10.25
1
0
Run&Stop
03F6H
P10.16
Set time is
meet
0: No
1: Meet
1
Actual
Actual
03F7H
P10.17
Control
channel is
switched to
terminal
0: No action
1: Control channel is
terminal
1
Actual
Actual
03F8H
P10.18
Keypad
disconnected
with drive
0: Carry on running
1: Stop
Note: Keypad control
mode.
1
1
Stop Only
03F9H
P10.19
Load default
after remove
User Code by
hardware
0: No
1: Load default
1
0
Run&Stop
03FAH
P10.20
Forced DC
brake
0: Off
1: On
1
Actual
Actual
03FBH
P10.21
PID output
keep
0: Off
1: On
1
Actual
Actual
03FCH