Appendix
VFD700 AC Drive Getting Started Guide
107
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P04.50
PLC step16
running time
0.0
~
6553.5
0.1
0.0
Run&Stop
01C1H
P04.51
PLC step16
Accel/Decel.
Rate selector
0: Accel./Decel. rate 1
1: Accel./Decel. rate 2
2: Accel./Decel. rate 3
3: Accel./Decel. rate 4
1
0
Run&Stop
01C2H
P04.52
PLC
operating
time unit
0: Second
1: Hour
1
0
Run&Stop
01C3H
P04.53
PLC finished
indicator
0: Not finished
1: Finished
1
Actual
Actual
01C4H
P04.54
PLC recycle
mode
indicator
0: No-recycle
1: Recycle
1
Actual
Actual
01C5H
P04.55
PLC reset
indicator
0
:
off
1
:
on
1
Actual
Actual
01C6H