Operation manual
VFD700 Series
High Performance Universal Inverter
More options please visit:www.veikong-electric.com
Страница 1: ...Operation manual VFD700 Series High Performance Universal Inverter More options please visit www veikong electric com...
Страница 2: ...toperating For further technical information and guide you can download the VFD700 Advanced User Manual from the website http www veikong electric com We will update and improve the manual termly and...
Страница 3: ...reactor dimensions 16 2 2 Mechanical installation 18 2 2 1Drive installation diagram 18 2 2 2 How to fit and remove the terminal cover 19 2 2 3How to fit and remove the keypad 20 2 3 Electrical instal...
Страница 4: ...75 5 3 Other issues 76 6 Maintenance 78 6 1 Routine maintenance 78 6 2 Periodic check 78 6 3 Parts replacement 80 6 4 Drive storage 80 6 5 Disposal 80 Appendix 81 1 Communication 81 2 Parameter list...
Страница 5: ...ile function 132 Menu P15 PID Controller 134 Menu P16 Programmable logic and binary sum 137 Menu P17 Threshold and variable selector 139 Menu P18 Brake logic control 144 3 Multistage velocity setup gu...
Страница 6: ...d electrician Install the drive on nonflammable materials like metalsheet in case of fire Do not install the drive in environment with explosive gas Even when the motor is stopped dangerous voltage is...
Страница 7: ...er forreplacement The VFD700 will start up automatically after an input voltage interruption if external running command is on Prior to measurements on the motor or the motor cable disconnect themotor...
Страница 8: ...0550 Power size 00040 0 4kW 45000 450kW 500kW Input phase D 1 3PH T 3PH Family Supply voltage 2 220V 4 380V 6 690V Brake unit 0 Built in brake 1 No brake unit Non Standard G type E small size G type P...
Страница 9: ...6 1 9 12 8 7 1 5 0 75 A VFD700 20D00150 6 3 0 20 5 11 3 8 1 5 A VFD700 20D00220 6 4 2 24 14 5 11 2 2 B VFD700 20D00400 6 6 7 30 4 16 5 17 6 4 C Table 1 2380V rating data Power supply 380VAC 480VAC 50...
Страница 10: ...0 E 3 205 301 310 160 231 340 350 185 J VFD700 40T18500 E 3 231 340 350 185 255 375 387 200 J VFD700 40T20000 E 3 255 375 387 200 280 415 427 220 J VFD700 40T16000 3 205 301 310 160 231 340 350 185 K...
Страница 11: ...209 170 175 160 237 192 198 185 K VFD700 60T18500 3 237 192 198 185 276 224 231 200 K VFD700 60T20000 3 276 224 231 200 327 266 274 250 K VFD700 60T25000 3 327 266 274 250 350 285 293 280 K VFD700 60...
Страница 12: ...ype 150 rated output current 1 minute P type 110 rated output current 1 minute V F 4 types V F user can program and ramp 2 0 power 1 7 power 1 2 power DC Braking Injection frequency 0 0 100 0 Max freq...
Страница 13: ...rmistor input Digital output terminals DO1 DO2 Programmable terminals Max output current 50mA DO2can be the terminal of output pulse 0 1kHz 50 0kHz and output PWM Analogue output AO1 programmable term...
Страница 14: ...rtage over current over load over voltage under Voltage Phase loss over heat heatsink and junction external fault etc Efficiency 1 5kW and below 89 2 2kW 22kW 93 30kW and above 95 Installation can be...
Страница 15: ...imension 2 1 1 Parts of drive Figure 2 1 Parts of VFD700 drive 2 1 2Diagram of mounting D W W1 H H1 Figure 2 2 Mechanical dimensions and mounting Size A B C EMC filter Link Terminal Cover Rating Label...
Страница 16: ...arted Guide 9 D W W1 W2 H1 H Figure 2 3Mechanical dimensions and mounting Size D E W W1 D D1 H H1 Figure 2 4Mechanical dimensions and mounting Size E1 F W W1 W2 H H1 D D1 Figure 2 5Mechanical dimensio...
Страница 17: ...uide W W1 W2 D D1 H H1 Figure 2 6Mechanical dimensions and mounting Size J W W1 W2 H H1 D D1 Figure 2 7Mechanical dimensions and mounting Size K D1 W2 H1 W W1 H D Figure 2 8 Mechanical dimensions and...
Страница 18: ...D700 20D00150 VFD700 40T00075 VFD700 40T00150 VFD700 40T00220 E B VFD700 20D00220 142 4 123 5 220 4 208 155 5 5 2 2 VFD700 40T00220 VFD700 40T00400 VFD700 40T00550 E VFD700 40T00550 P C VFD700 20D0040...
Страница 19: ...60T05500 VFD700 60T07500 G VFD700 40T09000 445 6 340 170 725 701 5 355 349 5 10 63 VFD700 40T11000 VFD700 40T13200 VFD700 60T09000 VFD700 60T11000 VFD700 60T13200 J VFD700 40T16000 E 575 5 440 220 937...
Страница 20: ...Hole Weight kg K1 VFD700 40T31500 E 720 579 194 1595 5 1553 5 483 477 5 13 VFD700 40T35500 E VFD700 60T31500 E VFD700 60T35500 E L VFD700 40T31500 804 2200 804 350 VFD700 40T35500 VFD700 40T40000 VFD...
Страница 21: ...45 85 54 5 3 Mounting hole for countersunk head phillips slot screw GB T819 1M4 12 Location pillar 6 Mounting hole for countersunk head phillips slot screw GB T819 1M4 12 Location pillar 6 Figure 2 11...
Страница 22: ...ted Guide 15 2 1 4 Simple keypad pallet Figure 2 13Outlook of Simple keypad pallet 114 7 105 6 64 5 70 6 53 0 31 37 5 35 5 1 5 1 5 17 3 Figure 2 14Outline dimensions of simple keypad pallet 106 6 65 5...
Страница 23: ...d d1 h h1 f Mounting hole R L Copper bar mounting hole K Reactor weight kg VFD700 40T05500 167 108 153 5 95 163 5 131 158 5 10 15 9 10 3 VFD700 40T07500 VFD700 40T09000 190 160 153 117 245 192 180 10...
Страница 24: ...VFD700 60T09000 190 160 153 117 245 192 180 10 15 12 20 VFD700 60T11000 VFD700 60T13200 VFD700 60T16000 E 190 160 148 115 245 192 250 10 20 13 25 VFD700 60T18500 E VFD700 60T20000 E VFD700 60T16000 2...
Страница 25: ...of VFD700 60T31500E and VFD700 60T35500E are AC Reactor whose dimensions are as follows 13 Figure 2 18 Dimensions of Externeal AC Reactor Size K1 690V_ 2 2 Mechanical installation 2 2 1Drive installat...
Страница 26: ...drives cool Air flowshould be drawn in and expelled as illustrated inthe left picture 2 2 2 How to fit and remove the terminal cover H z P R O G M O D E A K ey pa d C on tr ol V ES C PR O M O D RU N S...
Страница 27: ...correct angle into the slots on the control pod and then push down the keypad VFD700 keypad is removable and can be linked to the drive with a standard net cable shown as below port converter Figure...
Страница 28: ...to DC1 DC Negative DC bus U V W Output terminals Motor terminals PE Protective earth terminal NOTE Size C has DC reactor inside DC1 is not used For size C the brake resistor is connected to BR and DC...
Страница 29: ...om factory BR Brake resistor the other side of the resistor is connected to DC DC Negative DC bus U V W Output terminals Motor terminals PE Protective earth terminal Models of size F VFD700 T03000 VFD...
Страница 30: ...r side of the resistor is connected to DC1 DC Negative DC bus U V W Output terminals Motor terminals PE Protective earth terminal Models of size G VFD700 T09000 VFD700 T13200 L1 L2 L3 PE PE U V W DC D...
Страница 31: ...de of the resistor is connected to DC DC Negative DC bus U V W Output terminals Motor terminals PE Protective earth terminal Models of size K VFD700 T16000 VFD700 T28000 Size K DC1 DC DC BR DC U V W P...
Страница 32: ...wer terminal functions of size K1 Terminals Function L1 L2 L3 AC power supply DC PositiveDC bus BR Brake resistor the other side of the resistor is connected to DC DC Negative DC bus U V W Output term...
Страница 33: ...C DC Negative DC bus U V W Output terminals Motor terminals PE Protective earth terminal NOTE In VFD700 T the first means 4 or 6 and the second means 0 or 1 2 3 2Power connections L1 L2 L3 L1 L2 L3 N...
Страница 34: ...Power Control cable mm2 IEC gG A 30A CC class 30A T class A Input current A Supply cable mm2 Motor cable mm2 1PH 3PH 1PH 3PH 1 3PH 1PH 3PH 3PH VFD700 20D00040 10 8 10 8 7 1 4 1 5 1 0 1 0 0 5 VFD700 20...
Страница 35: ...00 415 120 2 120 2 0 5 VFD700 40T16000 450 500 340 120 2 120 2 0 5 VFD700 40T18500 500 500 375 120 2 120 2 0 5 VFD700 40T20000 630 600 457 120 2 120 2 0 5 VFD700 40T25000 670 505 150 2 150 2 0 5 VFD70...
Страница 36: ...500 375 120 2 120 2 0 5 VFD700 60T35500 500 500 413 120 2 120 2 0 5 VFD700 60T31500 E 500 500 375 120 2 120 2 0 5 VFD700 60T35500 E 500 500 413 120 2 120 2 0 5 VFD700 60T40000 630 600 468 120 2 120 2...
Страница 37: ...W 24V User 24V DC DC1 DC BR DC choke Motor CN3 CN2 Keypad connector Option connector Common PE PE HD700 Supply 1 3 PH A B 485 terminals RJ45 port Drive Brake resistor Programmable L1 L2 0V 10V 0 4 mA...
Страница 38: ...DI5 Programmable digital input terminals The common can be 0V or 24V by setting P09 21 default is 0V Input resistance 10 k High low logic threshold 10V 1V Samplingperiod 1ms DI6 Normal digital input...
Страница 39: ...ue input1 0V 10V Input resistance 100k 0 4 mA 20mA Load resistance 188 Min Potentiometer resistance 0 5k Resolution 0 1 Accuracy 2 Sampling period 5ms AI2 Programmable analogue input 2 0V 10V Input re...
Страница 40: ...efault only basic function for digital input P09 01 1 advanced functions are available for digital input This manual only introduces the basic function of digital input The basic function list is as t...
Страница 41: ...V P09 21 1 common is 24V Different connection types of DI and common are as showed in table 2 17 Table 2 18 Digital input connection examples P09 21 Connection P09 21 0 Source P09 21 1 Sink Switch typ...
Страница 42: ...0 DI DI 24V HD700 24V 0V DC 24V Internal circuit P09 21 1 DI DI HD700 24V 0V DC 24V Internal circuit OC PNP By inner 24V P09 21 0 DI DI 24V HD700 24V 0V K1 K2 Internal circuit P09 21 1 DI DI HD700 24V...
Страница 43: ...PTC Figure 2 39 PTC thermistor connection Digital output There are 2 digital output terminals all OC type 24V output DO2can be set as high frequency pulse output when using the DO to drive relay pleas...
Страница 44: ...s two Analogue input channels HD700 10V AI1 0V AI2 10V 0V 10V 0V 0 4 mA 20mA Figure 2 41Analogue input connection Analogue output Output is voltage 0V 10V maximum output current is 5mA HD700 AO1 0V Ou...
Страница 45: ...resistor specification Spec Model Min resistance Max brake current A Peak power kW Recommended resistance VFD700 40T00075 120 7 5 67 240 VFD700 40T00150 120 7 5 67 240 VFD700 40T00220 E 120 10 5 67 2...
Страница 46: ...984 1 4 VFD700 40T45000 0 7 1200 984 1 4 Table 2 21 690Vsupply voltage brake resistor specification Spec Model Min resistance Max brake current A Peak power kW Recommended resistance VFD700 60T03000...
Страница 47: ...is recommended Cable clearance Don t place control cable in a zone extending 300mm around the drive and power cables 2 3 7EMC Filter Optional RFI filter Place the RFI filter to the drive as close as...
Страница 48: ...kage protecting contactor is used for front power supply the internal EMC filter should be removed Fit and remove the internal EMC filter There is a metal link between the ground and EMC filter as sho...
Страница 49: ...D E Tighten the filter capacitor grounding screw and fit the internal EMC filter Untighten the filter capacitor grounding screw and disconnect the internal EMC filter NOTE When disconnectingvaristor...
Страница 50: ...and then remove the EMC filter NOTE In order to ensure reliable earthing please tighten the screws 1 2 after removing the EMC filter 1 2 Figure 2 48 Fit and remove the internalEMC filter Size G Untig...
Страница 51: ...nd then remove the EMC filter NOTE In order to ensure reliable earthing please tighten the screws after removing the EMC filter 1 2 Figure 2 50 Fit and remove the internalEMC filter Size K Untighten s...
Страница 52: ...make screw1 unscrewed and disconnect wiring Wiring to screw 2is suggested to avoid the EMC wiring contacting other parts of the drive 1 2 Figure 2 52 Fit and remove the internalEMC filter Size L If y...
Страница 53: ...own below Figure 3 1 LED keypad 3 1 1 LED lights LED display can show the drive status parameters and value fault warninginformation etc Run light is on the upper right corner of the key of when drive...
Страница 54: ...hen in keypad control mode P00 03 or P10 07 0 pressing this key will make the drive run Stop the switch will stop the drive unless the keypad is locked totally Reset the drive if the keypad is not loc...
Страница 55: ...current Output voltage 0 0 0 537 Figure 3 2 Display switchover flow If P05 02 is set to 1 In standby mode normal display is reference frequency Operation procedure is as figure 3 3 0 0 0 00 0 537 0 00...
Страница 56: ...hange and will return to level 2 current parameter pressing ESC again will return level 1 Only after pressing PRG can the change of parameter value be effective If there s no digit flashing for a para...
Страница 57: ...6 Editing parameter flow Lock and unlock the keypad To avoid wrong keypad operation VFD700 has the function of keypad locking by setting P05 06 if the value of P05 06 is 0 all the keys are available...
Страница 58: ...he keypad will show the normal display selected by P05 01 If the PIN is 8 and the user code function is as on Enable stage following figure 3 8 shows how to pass the PIN verifying 0 00 P00 P00 01 8 0...
Страница 59: ...splay After finishing the autotune the drive will stop and P00 17 will be 0 3 2 Drive control 3 2 1 Drive status VFD700 drive status is defined as Ready Stop Running Editing Auto tune Trip and Alarmin...
Страница 60: ...d will keep this cycle until the alarm is removed The parameter P12 13 can be set to display the alarm information or not 3 2 2 Control modes Through P00 03 P10 07 there are 3 control modes 0 Keypad 1...
Страница 61: ...valid P04 17 0 Textile valid P14 01 0 Jog order NO Figure 3 10 VFD700 Running mode Priority 3 3 Quick commissioning 3 3 1Keypad control Use the parameter menu0 to explain the drive setup as below Tab...
Страница 62: ...eference is from AI1 P00 13 motor nameplate data Set the motor rated voltage P00 14 motor nameplate data Set the motor rated current P00 15 motor nameplate data Set the motor rated frequency P00 16 mo...
Страница 63: ...trol P09 22 0 3 wire is disabled 2 wire control P09 22 1 3 wire control mode 1 P09 22 2 3 wire control mode 2 When P09 22 1 3 wire control mode 1 is selected DI1 DI2 DI3 are automatically set as below...
Страница 64: ...en drive will stop P09 04 6 DI3 is FWD REV input Voltage control Wiring is as figure 3 13 HD700 DI1 DI2 DI3 SB1 SB2 K 0V 24V Figure 3 13 3 wire control mode2 connection SB1 Run button SB2 Stop button...
Страница 65: ...arize most popular parameters into MenuP00 In this VFD700 User manual we only introduce Menu P00 parameters for total function and technical data explanation please read the VFD700 Advanced User Manua...
Страница 66: ...cycle display order in standby or running state the order of keypad cycle display will not be changed P05 01 P05 13 P05 12 P05 14 P01 14 ESC ESC ESC ESC 1 Auto switch mode in running state Keypad cyc...
Страница 67: ...OWN functionthe reference can be changed For example Define the DI4 and DI5 as UP and DOWN respectively and the setup is as below P09 05 8 DI4 function is UP P09 06 9 DI5 function is DOWN 2 Preset Con...
Страница 68: ...2 AI1is the Torque error About AI1signal mode there are current mode and voltage mode for details please refer to the explanation of parameter P00 05 P08 02 4 AI2 AI2 function is decided by the param...
Страница 69: ...ng without trip 6 0V 10V When the AI mode selection is 0 5 if the input current is over 26mA the drive will trip at F012 the drive will stop as the mode decided by P03 10 then turn off the IGBTs When...
Страница 70: ...10 0s After starting the drive output frequency will ramp from 0 00Hz to 50 00Hz and the acceleration rate is 10 0s 50 00Hz 100 00Hz 5 0s Parameter ID Parameter Name Range Default Change Mode P00 11 P...
Страница 71: ...ill be in ready status 2 Static autotune2 every run When P0 17 2 every run order will be received and the drive will do the autotune After the static autotune the result will be saved into the EEPROM...
Страница 72: ...ut voltage Vb fb fz Output frequency Ve Ve motor rated voltage Vb Boost voltage Ve P00 22 fZ boost close frequency P06 09 fb rated frequency Figure 4 1 Voltage boost Parameter ID Parameter Name Range...
Страница 73: ...ult 0 1 0 Stop Only 0 No action 1 Load default When P00 24 1 press PRG key and default setup will be loaded and saved into the EEPROM P00 24 0 NOTE After loading default except motor parameters all ot...
Страница 74: ...r cable and electric connection Acceleration or deceleration time is too short Increase accel or decel time The motor is still spinning when the drive is reset after sudden stop Choose P03 05 and set...
Страница 75: ...short circuit Turn off the IGBTs the drive can be reset 10s after trouble removal Brake resistor trouble Check the brake resistance and the cabling Internal fault Contact service center F007 Heatsink1...
Страница 76: ...emoval V F is not right Setup V F and voltage boost correctly Supply voltage is low Check the power supply and cabling Motor load is jammed or the load change is excessive Check the motor load The fac...
Страница 77: ...4V F015 Parameter copying fault the drive can be reset 1s after trouble removal Parameter copying is abnormal Power up again downloading the parameter setup to the drive when keypad EEPROM is empty Up...
Страница 78: ...r other external options contact service center F020 EEPROM reading and writing failure Error occurs when reading writing the control word Press STOP key to reset the drive and try again contact servi...
Страница 79: ...reset Fan blade not rotating correctly Check the fan blades Wiring is wrong Check fan wiring Contact service center F033 Current sense fault Turn off IGBTs and the drive can not be reset Internal fau...
Страница 80: ...r failed Turn off IGBTs and the drive can not be reset IGBT failure Contact service center F040 Software exception Turn off IGBTs and the drive can not be reset Software error Contact service center M...
Страница 81: ...sturbance EEPROM reading writeing fault F020 When the trip occurs user can load default and then reset the drive Odinary trips F001 F006 The drive can be reset 10s after trouble removal Other trips Th...
Страница 82: ...4 P13 07Motor1 rated current Check the motor cable Properly increase the acceleration and decelerationtimes Set P03 05to the correct start mode speed tracking and restart H002 Motor overload is integr...
Страница 83: ...0 If the reference source is analogue is there correct analogue input signal If P09 21 is set correctly correct common point Parameter setup issue If the control channel is set correctly P00 03 If th...
Страница 84: ...according to the motor nameplate parameters can not be written Change is limited the parameter can onlybe changedin stop state The parameter property is actual Keypad is locked Press and hold ESC key...
Страница 85: ...normal Daily cleaning Try to keep the drive tidy Remove dust from drive surface avoid dust coming into the drive especially metal dust Effectively clean the oil stuff from the fan surface 6 2 Periodi...
Страница 86: ...Normal Whether there is dirty or dustattached to conductors Clean Normal Power terminal Whether they are broken Visual check and ask for service Normal Brake resistor Whether there is smell or broken...
Страница 87: ...below It is better to keep the drive in the original factory package After long time storage the drive s capacitors must be dealt with once again NOTE The starting pointof storage time is not purchasi...
Страница 88: ...lectric functions A serial communications link enables one or more drives to be used in a system controlled by a host controller such as a PLC or computer HD700 A B RS485 RS485 PE Upper computer A fig...
Страница 89: ...nction codes The function code determines the different requests A table 1 1 Function code Code Hex Description 03H Read multiple registers 06H Write single register value changes cannot be saved when...
Страница 90: ...Of Register Read CRC Checking MSB LSB MSB LSB LSB MSB 01H 03H 01H 90H 00H 0AH C4H 1CH Slave VFD700 drive Response Drive Node Code Number Of Register Read Contents of P04 01 P04 10 Check Sum Of CRC P04...
Страница 91: ...hCRCHi 0x00 0xC1 0x81 0x40 0x01 0xC0 0x80 0x41 0x01 0xC0 0x80 0x41 0x00 0xC1 0x81 0x40 0x01 0xC0 0x80 0x41 0x00 0xC1 0x81 0x40 0x00 0xC1 0x81 0x40 0x01 0xC0 0x80 0x41 0x01 0xC0 0x80 0x41 0x00 0xC1 0x8...
Страница 92: ...0x1F 0xDD 0x1D 0x1C 0xDC 0x14 0xD4 0xD5 0x15 0xD7 0x17 0x16 0xD6 0xD2 0x12 0x13 0xD3 0x11 0xD1 0xD0 0x10 0xF0 0x30 0x31 0xF1 0x33 0xF3 0xF2 0x32 0x36 0xF6 0xF7 0x37 0xF5 0x35 0x34 0xF4 0x3C 0xFC 0xFD...
Страница 93: ...ned short type unsigned short CCRC_ModbusRTUCRC16 unsigned char puchMsg short usDataLen unsigned short ReturnValue high byte of CRC initialized unsigned char uchCRCHi 0xFF low byte of CRC initialized...
Страница 94: ...lse 7 Fieldbus option 8 User programmed 0 Run Stop 0003H 0064H P03 27 Comms control word 0 65535 0 Run Stop 0146H P03 28 Comms control word enable 0 1 0 Run Stop 0147H P10 02 Address 0 247 1 Run Stop...
Страница 95: ...on 0 Drive enable 1 Run 2 3 wire enable 3 Run forward 4 Run reverse 5 FWD REV 6 Jog forward 7 Jog reverse 8 Fault reset 9 Saving parameters 10 Clean the trip tracking log 11 Enable comms to write para...
Страница 96: ...running is over 15 PLC is working Scale definition Frequency 1 100 If the drive reference is 50 00Hz then for hex it is 1388H Time rate 1 10 If the acceleration rate is 10 0s then for comms hex it is...
Страница 97: ...running state 2 Reserved 1 0 Run Stop 0000H P00 02 Parameter display control P05 03 0 Only P00 parameters 1 All menu parameters 2 Only parameters which are different from the default setup 1 1 Run Sto...
Страница 98: ...current loosing without trip 6 0V 10V 1 6 Stop Only 0004H P00 06 Preset1 P04 01 Max reference 0 01Hz 5 00Hz Run Stop 0005H P00 07 Max frequency P01 02 0 00Hz 300 0Hz 0 01Hz 50 00Hz Stop Only 0006H P0...
Страница 99: ...P00 14 Motor1 rated current P13 07 G or P type 0 1A rated current 1 2 GP type 0 1A P type rated current 0 1A By model Stop Only 000DH P00 15 Motor1 rated frequency P13 08 1 00Hz 300 0Hz 0 01Hz 50 00H...
Страница 100: ...loop vector control 1 2 Open loop vector control 2 1 0 Stop Only 0013H P00 21 Switch frequency P10 10 1kHz 15kHz 1kHz By model Run Stop 0014H P00 22 Voltage boost P06 08 0 0 30 0 0 1 By model Run Sto...
Страница 101: ...1 03 Minimum frequency 0 00Hz Max frequency 0 01Hz 0 00Hz Stop Only 0066H P01 04 Jog frequency 0 00Hz P01 02 0 01Hz 5 00Hz Run Stop 0067H P01 05 Skip frequency1 0 00Hz Max frequency 0 01Hz 0 00Hz Stop...
Страница 102: ...71H P01 15 Preset select bit 0 status 0 On 1 Off 1 Actual Actual 0072H P01 16 Preset select bit1 status 0 On 1 Off 1 Actual Actual 0073H P01 17 Preset select bit2 status 0 On 1 Off 1 Actual Actual 007...
Страница 103: ...n 1 Actual Actual 007CH P01 26 Reference source is switched to AI2 0 Off 1 On 1 Actual Actual 007DH P01 27 User programmed reference display max frequency max frequency 0 01Hz Actual Actual 007EH P01...
Страница 104: ...n Stop 00CFH P02 09 Deceleration rate 3 0 0 3600 0 0 1 30 0 Run Stop 00D0H P02 10 Accelerationrate 4 0 0 3600 0 0 1 30 0 Run Stop 00D1H P02 11 Deceleration rate 4 0 0 3600 0 0 1 30 0 Run Stop 00D2H P0...
Страница 105: ...te 0 1s 600 0s 0 1s 10 0s Run Stop 00DEH P02 24 Jog interval time 0 1s 600 0s 0 1s 0 1s Run Stop 00DFH P02 25 UP DN output negative permit 0 Only positive 1 Negative permit 1 0 Run Stop 00E0H P02 26 U...
Страница 106: ...t power off 2 0 only can be changed when drive is active 3 Running reference of last power off only can be changed when drive is active 4 Preset 1 UP DOWN and reset are active at all times 5 Preset 1...
Страница 107: ...function 1 2 enable function 2 1 0 Stop Only 012EH P03 04 Waiting time for auto start 0 0s 60 0s 0 1s 0 0s Run Stop 012FH P03 05 Start mode 0 Start directly 1 First DC injection then start 2 speed tr...
Страница 108: ...DC injecting current 0 0 300 0 refer to the motor rated current 0 1 0 0 Run Stop 0138H P03 14 Stop DC injecting time 0 0s 60 0s 0 1s 0 0s Run Stop 0139H P03 15 Dynamic brake control 0 Disabled 1 Enab...
Страница 109: ...On 1 0 Actual 0142H P03 24 FWD REV 0 Forward 1 Reverse 1 0 Actual 0143H P03 25 Jog forward 0 Off 1 On 1 0 Actual 0144H P03 26 Jog reverse 0 Off 1 On 1 0 Actual 0145H P03 27 Comms control word 0 65535...
Страница 110: ...1Hz 10 00Hz Run Stop 0198H P04 10 Preset 10 0 01Hz 20 00Hz Run Stop 0199H P04 11 Preset 11 0 01Hz 30 00Hz Run Stop 019AH P04 12 Preset 12 0 01Hz 40 00Hz Run Stop 019BH P04 13 Preset 13 0 01Hz 45 00Hz...
Страница 111: ...Decel rate 3 3 Accel Decel rate 4 1 0 Run Stop 01A6H P04 24 PLC step3 running time 0 0 6553 5 0 1 0 0 Run Stop 01A7H P04 25 PLC step3 Accel Decel rate selector 0 Accel Decel rate 1 1 Accel Decel rate...
Страница 112: ...Decel rate 3 3 Accel Decel rate 4 1 0 Run Stop 01B0H P04 34 PLC step8 running time 0 0 6553 5 0 1 0 0 Run Stop 01B1H P04 35 PLC step8 Accel Decel Rate selector 0 Accel Decel rate 1 1 Accel Decel rate...
Страница 113: ...Decel rate 3 3 Accel Decel rate 4 1 0 Run Stop 01BAH P04 44 PLC step13 running time 0 0 6553 5 0 1 0 0 Run Stop 01BBH P04 45 PLC step13 Accel Decel rate selector 0 Accel Decel rate 1 1 Accel Decel rat...
Страница 114: ...Decel Rate selector 0 Accel Decel rate 1 1 Accel Decel rate 2 2 Accel Decel rate 3 3 Accel Decel rate 4 1 0 Run Stop 01C2H P04 52 PLC operating time unit 0 Second 1 Hour 1 0 Run Stop 01C3H P04 53 PLC...
Страница 115: ...s different with default 1 1 Run Stop 01F6H P05 04 Parameter copying 0 No action 1 uploading parameters to keypad 2 downloading parameters to the drive 1 0 Stop Only 01F7H P05 05 LCD language 0 Chines...
Страница 116: ...urrent 0 1A Actual Actual 0201H P05 15 Torque current 0 0A 3 motor rated current 0 1A Actual Actual 0202H P05 16 Magnetizing current 3 motor rated current 3 motor rated current 0 1A Actual Actual 0203...
Страница 117: ...Actual Actual 020DH P05 27 Drive is running 0 Drive is at ready or trip stage 1 Drive is running 1 Actual Actual 020EH P05 28 Rated load is reached 0 Output current is less than motor rated current 1...
Страница 118: ...06 P06 02 0 01Hz 0 00Hz Stop Only 025BH P06 05 V F voltage 2 P06 07 P06 03 0 1 0 0 Stop Only 025CH P06 06 V F frequency 1 0 00 P06 04 0 01Hz 0 00Hz Stop Only 025DH P06 07 V F voltage 1 0 P06 05 0 1 0...
Страница 119: ...del Run Stop 02BEH P07 04 P07 11 Reserved P07 12 Current controller Kp gain 0 001 10 000 0 001 0 020 Run Stop 02C7H P07 13 Current controller Ki gain 0 00s 100 00s 0 01s 0 20s Run Stop 02C8H P07 14 Cu...
Страница 120: ...Hz 50 00 Hz Run Stop 02CDH P07 19 Torque mode reference source 0 Keypad 1 AI1 2 AI2 3 Pulse DI7 4 Serial comms 5 User programmed 6 Optional module 1 1 Stop Only 02CEH P07 20 Torque gain 0 0 300 0 0 1...
Страница 121: ...mA 2 4mA 20mA current loosing with trip 3 20mA 4mA current loosing with trip 4 4mA 20mA current loosing without trip 5 20mA 4mA current loosing without trip 6 0V 10V 1 6 Stop Only 0321H P08 03 AI1 fun...
Страница 122: ...99 Advanced function 1 0 Stop Only 0327H P08 09 AI2 offset 200 0 200 0 0 1 0 0 Run Stop 0328H P08 10 AI2 scaling 0 000 20 000 0 001 1 000 Run Stop 0329H P08 11 AI2 inverter 0 Off 1 On 1 0 Run Stop 03...
Страница 123: ...n 1 0 Run Stop 032DH When AO1 select the following function and 100 output 0 Output frequency Maximum running frequency 1 Reference frequency Maximum running frequency 2 Active current 3 times motor r...
Страница 124: ...H P08 19 Analogue output level 0 0 100 0 0 1 Actual Actual 0332H P08 20 AI1 upper limit 0 0 100 0 0 1 100 0 Run Stop 0333H P08 21 AI1 lower limit 0 0 P08 20 0 1 0 0 Run Stop 0334H P08 22 AI2 upper lim...
Страница 125: ...et select bit 1 2 Run 3 Run forward FWD 4 Run reverse REV 5 3 wire enable 6 FWD REV 7 Jog forward 8 UP 9 DOWN 10 Enable 11 Reset 12 Control channel is switched to terminal 13 Reset length counting 14...
Страница 126: ...4 Under voltage trip 5 PLC finished 6 Frequency is arrival 7 Torque limit is working 8 Time arrival 9 Overload is calculating 10 At zero speed 11 Brake logic is on 12 No function 99 Advanced function...
Страница 127: ...sabled 1 3 wire 1 2 3 wire 2 1 0 Stop Only 0399H P09 23 DI6 mode 0 Normal digit 1 Length counting pulse 2 Number counting pulse 1 0 Run Stop 039AH P09 24 DI7 mode 0 Normal digit 1 Motor thermister 2 H...
Страница 128: ...2 Drive is alarming 3 100 current 4 Drive healthy 5 Length counting arrival 6 Running at zero speed 7 Brake logic is on 8 No function 99 Advanced function 1 DO1 6 Run Stop 03A1H P09 31 DO2 function D...
Страница 129: ...4 DI5 status 0 Off 1 On 1 Actual Actual 03AFH P09 45 DI6 status 0 Off P09 23 0 1 On 1 Actual Actual 03B0H P09 46 DI7 status 0 Off P09 24 0 1 On 1 Actual Actual 03B1H P09 47 Relay1 status 0 Off 1 On 1...
Страница 130: ...4 Comms configuration 0 8 1 N RTU without checking 1 8 2 N RTU without checking 2 8 1 0 RTU with odd bit checking 3 8 1 E RTU with even bit checking 1 1 Run Stop 03EBH P10 05 Response delay time 0ms 2...
Страница 131: ...ctual 03F5H P10 15 Set operation time 0 P10 25 1 0 Run Stop 03F6H P10 16 Set time is meet 0 No 1 Meet 1 Actual Actual 03F7H P10 17 Control channel is switched to terminal 0 No action 1 Control channel...
Страница 132: ...r off stop mode 0 Coasting stop 1 Ramp stop 1 0 Stop Only 03FDH P10 23 Cumulative running time reset 0 Off 1 On 1 0 Run Stop 03FEH P10 24 Set the unit of running time 0 Hour 1 Second 1 0 Stop Only 03F...
Страница 133: ...08 Trip 8 0453H P11 09 Trip 9 0454H P11 10 Last trip 0455H P11 11 Last trip frequency P01 02 P01 02 0 01Hz Actual Actual 0456H P11 12 Last trip current 0 0A 3 motor rated current 0 1A Actual Actual 04...
Страница 134: ...re overload alarm 0 Off 1 On 1 1 Stop Only 04B3H P12 05 Pre overload threshold 80 0 150 0 0 1 130 0 Run Stop 04B4H P12 06 Pre overload delay time 0 0s 60 0s 0 1s 5 0s Run Stop 04B5H P12 07 Auto reset...
Страница 135: ...04BCH P12 14 External fault 0 Off 1 On 1 0 Run Stop 04BDH P12 15 Reset trip 0 Off 1 On 1 0 Stop Only 04BEH P12 16 Under voltage indicator 0 Off 1 On 1 Actual Actual 04BFH P12 17 Overload accumulator...
Страница 136: ...run once a time 3 Reserved 1 0 Stop Only 0515H P13 03 Motor 1 motor 2 select 0 Motor 1 1 Motor 2 1 0 Stop Only 0516H P13 04 Reserved P13 05 Motor 1 power factor 0 00 1 00 0 01 0 85 Stop Only 0518H P13...
Страница 137: ...00 0 001 0 Stop Only 051EH P13 12 Reserved P13 13 Motor 1 transient inductance 0 00 50 00 0 01 by model Stop Only 0520H P13 14 P13 16 Reserved P13 17 Motor 2 power factor 0 00 1 00 0 01 0 85 Stop Only...
Страница 138: ...of motor 2 pairs of pole 0 Auto 1 2 pole 2 4 pole 3 6 pole 4 8 pole 1 2 Stop Only 0528H P13 22 Motor 2 rated speed 1rpm 60000pm 1rpm 0rpm Stop Only 0529H P13 23 Motor 2 stator resistance 0 000 60 000...
Страница 139: ...0 map to P14 02 0 1 0 0 Run Stop 057CH P14 06 Jump frequency 0 0 50 0 map to P14 05 0 1 0 0 Run Stop 057DH P14 07 Textile period 0 1 s 1000 0s 0 1s 10 0s Run Stop 057EH P14 08 Triangle rise time 0 0 1...
Страница 140: ...al number meets set number 0 Lees than P14 15 1 Equals P14 15 1 Actual Actual 0588H P14 18 Reset length counting 0 Off 1 On 1 0 Run Stop 0589H P14 19 Reset number counting 0 Off 1 On 1 0 Run Stop 058A...
Страница 141: ...feedback inverter 0 Off 1 On 1 0 Run Stop 05E0H P15 06 PID reference slew rate 0 0s 3200 0s 0 1s 0 0 Run Stop 05E1H P15 07 PID enable 0 Off 1 On 1 0 Run Stop 05E2H P15 08 Reserved P15 09 PID proporti...
Страница 142: ...error level 100 0 100 0 0 1 Actual Actual 05F0H P15 22 PID output level 100 0 100 0 0 1 Actual Actual 05F1H P15 23 Sleep mode enable 0 Off 1 On 1 0 Stop Only 05F2H P15 24 Sleep channel selector P00 00...
Страница 143: ...Mode Modbus Register Address P15 31 Reserved P15 32 Reserved P15 33 Reserved P15 34 Sleep status indicator 0 Not sleep mode 1 Sleep mode 1 Actual Actual 05FDH NOTE Pxx xx means the value of Pxx xx NOT...
Страница 144: ...45H P16 07 block1 output function P00 00 P18 08 0 01 P00 00 Stop Only 0646H P16 08 Block2 source1 P00 00 P18 08 0 01 P00 00 Stop Only 0647H P16 09 Block2 source1 inverter 0 Off 1 On 1 0 Run Stop 0648H...
Страница 145: ...utput function P00 00 P18 08 0 01 P00 00 Stop Only 0652H P16 20 Block1 output indicator 0 Off 1 On 1 Actual Actual 0653H P16 21 Block2 output indicator 0 Off 1 On 1 Actual Actual 0654H P16 22 Sum outp...
Страница 146: ...P00 00 Stop Only 06A8H P17 06 Threshold block2 source P00 00 P18 08 0 01 P00 00 Stop Only 06A9H P17 07 Threshold block2 threshold 0 0 100 0 0 1 0 0 Run Stop 06AAH P17 08 Threshold block2 hysteresis 0...
Страница 147: ...put input1 9 Raise to power P17 16 0 02 output input1 2 100 P17 16 0 03 output input1 3 1002 P17 16 has any other value output input1 Note P17 16 means the value of P17 16 P17 16 Variable selector1 co...
Страница 148: ...r P17 23 0 02 output input1 2 100 P17 23 0 03 output input1 3 1002 P17 23 has any other value output input1 Note P17 23 means the value of P17 23 P17 23 Variable selector2 control factor 0 00 99 99 0...
Страница 149: ...t1 2 100 P17 30 0 03 output input1 3 1002 P17 30 has any other value output input1 Note P17 30 means the value of P17 30 P17 30 Variable selector3 control factor 0 00 99 99 0 01 0 00 Run Stop 06C1H P1...
Страница 150: ...User defined bit variable 5 0 1 1 0 Run Stop 06CCH P17 42 User defined word variable 1 300 0 300 0 0 1 0 0 Run Stop 06CDH P17 43 User defined word variable 2 300 0 300 0 0 1 0 0 Run Stop 06CEH P17 44...
Страница 151: ...50 Run Stop 0709H P18 03 Brake apply current threshold 0 200 1 10 Run Stop 070AH P18 04 Brake release frequency threshold 0 00Hz 20 00Hz 0 01Hz 1 00Hz Run Stop 070BH P18 05 Brake apply frequency thre...
Страница 152: ...is not preset terminal status is as shown below Table 4 2 Preset and preset terminal status corresponding table 2 DI5 Status bit 1 DI4 Status bit 0 Speed OFF OFF Keep the frequency setting OFF ON Pres...
Страница 153: ...in following table Preset and the preset terminal mapping table P01 18 P01 17 P01 16 P01 15 Reference selector P01 19 OFF OFF OFF OFF Preset1 1 OFF OFF OFF ON Preset2 2 OFF OFF ON OFF Preset3 3 OFF OF...
Страница 154: ...parameter P18 08 P00 00 P15 02 P18 08 P00 00 P15 03 Main reference source parameter P15 07 Drive states P12 01 P18 08 P00 00 P15 01 PID reference source parameter PID feedback source invert PID output...
Страница 155: ...simple application example M P DI1 0V AI1 0V 10V AI2 0V Input power HD700 Outside setting L1 L2 L3 N U V W Pressure feedback Pressure setting Pressure transmitter Figure 3 14 Constant water presser co...
Страница 156: ...KONG drives can realize high speed data communication with computers through HDOM 232 Communication adapter HDOM USB Can realize the isolate transformation bi directly between USB and RS 485 VEIKONG d...
Страница 157: ...3000 VFD700 61T03700 VFD700 61T04500 VFD700 61T05500 VFD700 60T07500 VFD700 60T09000 VFD700 60T11000 VFD700 60T13200 VFD700 61T07500 VFD700 61T09000 VFD700 61T11000 VFD700 61T13200 VFD700 40T16000 VFD...
Страница 158: ...lectromagnetic Compatibility EMC Directive 2004 108 EC the RoHS2 0 Directive2011 65 EUand the CE Marking Directive 93 68 EEC Printed Dale Lee R D Director Date August 26 2015 These electronic drive pr...
Страница 159: ...Tel no Fax no Product information Drive Family Power size kW S N Contract no Purchase date Repair record Service engineer Tel no Fixed date Fault information Complaints and demanding on our products...
Страница 160: ...not caused by drive quality issues is out of the free range From inappropriate negligent or incorrect installation or adjustment of the optional operating parameters of the equipment or from mismatch...