Zone attribute
Description
Tech Zone
Display
Allows an opening zone to be displayed on the system keypad. The alert led should also activate.
When areas are selected it will only be displayed on the keypad which is assigned to the area in
which the zone has been selected. The alert may only be displayed on the keypad when the area is
in the unset mode and not in the Part A, Part B and set mode.
Tech Zone
Audible
Allows an activated zone to operate the buzzer. This will operate the same as the Tech Zone
Display in the different setting modes and on systems with areas.
Tech Zone
Delay
Allows the zone to have a programmable delay. The delay is variable from 0 to 9999 seconds and
will apply to all Tech Zones. The operation is the same as the Mains Delay timer, if the zone is
closed within the delay time, then no alarm is sent to the ARC, no SMS is sent to the user and the
Technical Output will not trip.
Note:
The Technical Output will not trip until the delay timer has expired.
Armed report
only
Openings are reported only in armed mode.
Fire pre-alarm
If enabled and a fire alarm occurs, a Fire Pre-alarm timer is started and internal bells and buzzers
are activated. (See
on page 261.) If the alarm is not cancelled within the timer duration, a fire
alarm is confirmed, internal and external bells are triggered and an event is sent to ARC.
Fire
Recognition
If enabled, a Fire Recognition timer is activated which adds extra time to the Fire Pre-alarm timer
duration until a file alarm is reported for the zone. See
Seismic
Test/Automatic
Sensor Test
A Seismic zone type may be tested manually or automatically. This attribute allows automatic
testing to be enabled. See
on page 261 for details of how to configure the timer that
determines how often the panel tests any seismic zones that have this attribute set. The default
value for the timer is 7 days.
Timed
The ‘Timed’ attribute is used for Key Arm zones to delay the setting of an area. The delay follows
the exit timer for the area to which the key arm is associated.
Verification
Select the configured verification zone to assign to this zone to trigger audio/video verification.
Force Set
If enabled, the keyarm device can set the system, automatically inhibiting all open zones.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Appendix
© Vanderbilt 2018
386
A6V10276959-d
11.2018