Timer
Description
Default
External Bells
EXT BELL
TIME
Duration that external sounders will sound when alarm is activated. (0–999 minutes;
0 = never)
15min.
External Bell
Delay
EXT BELL
DELAY
This will cause a delayed activation of the external bell. (0–999 seconds)
0sec.
Chime
CHIME TIME
Number of seconds that a chime output will activate, when a zone with chime
attribute opens. (1–10 seconds)
2sec.
Confirmation
Confirm
CONFIRM
TIME
Note:
This option is only available for certain
Grade
and
Confirmation
option
combinations. (See
on page 252 and
This timer applies to the alarm confirmation feature and is defined as the maximum
time between alarms from two different non overlapping zones that will cause a
confirmed alarm. (0–60 minutes)
30min.
Confirmed
holdup
Note:
This option is only available for certain
Grade
and
Confirmation
option
combinations. (See
on page 252 and
This timer applies to the confirmed holdup feature and is defined as the maximum
time between alarms from two different non-overlapping zones that will cause a
confirmed alarm. (480–1200 minutes)
480min.
Dialer Delay
DIALER
DELAY
When programmed, the dialler delay initiates a predefined delay period before the
system dials out to an Alarm Receiving Centre (ARC). This is specifically designed to
reduce unwarranted responses from Alarm Receiving Centres and the constabulary.
In the event of a subsequent zone being tripped the dialler delay period is ignored and
the dialler dials out immediately. (0–999 seconds)
30sec.
Alarm abort
ALARM ABORT
Time after a reported alarm in which an alarm abort message can be reported. (0–999
seconds)
30sec.
Setting
Setting
Authorisation
SETTING
AUTH
Period for which Setting Authorisation is valid. (10–250 seconds)
20secs
Final Exit
FINAL EXIT
The Final Exit time is the number of seconds that arming is delayed after a zone
programmed with the final exit attribute is closed. (1–45 seconds)
7sec.
Bell on Fullset
FULLSET BELL
Activates the external bell momentarily to indicate a full set condition. (0–10 seconds)
0sec.
Fail To Set
FAIL TO SET
Number of seconds to display fail to set message on keypads (0 until valid PIN is
entered). (0–999 seconds)
10sec.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Engineer programming via the keypad
© Vanderbilt 2018
118
A6V10276959-d
11.2018