Zone Type
Processing
Category
Description
HOLD-UP ALARM
Hold-up
This zone type is active on a 24-hour basis and activated via a button. When
a Hold-up zone is activated it will report a Hold-up event, independent of
panel arming mode. The SILENT attribute is set by default therefore the
alarm will be silent. If unset, it will generate a full alarm. All activations are
logged and reported if log attribute is active.
TAMPER
Tamper
When open in the Unset mode, a Local Alarm is generated but no external
bell will activate. If the system is Full Set, a Full alarm is generated. If the
Security Grade of the system is set to Grade 3 then an engineer code is
required to restore the alarm.
TECHNICAL
Intruder
The tech zone controls a dedicated tech zone output. When a tech zone
changes state, the tech zone output will follow. That is:
l
When the tech zone opens, tech zone o/p triggers on
l
When the tech zone closes, tech zone o/p goes off
If more than one tech zone has been assigned, the tech zone output will
remain on until all tech zones are closed.
MEDICAL
Hold-up
This zone type is used in conjunction with radio or hardwired medical
switches.
Activation in any mode will:
l
Trigger the medical digital communicator output (unless Local attribute
is set)
l
Cause the panel buzzer to sound (unless Silent attribute is set)
l
Display the message Medic Alarm
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Appendix
© Vanderbilt 2018
380
A6V10276959-d
11.2018