Amount of current from Aux output using two 24Ah batteries (SPC535x/635x)
COMMS
NONE (mA)
PSTN (mA)
GSM (mA)
PSTN+GSM (mA)
Standby time
12 h
2205
2180
2165
2140
24 h
1650
1625
1610
1585
30 h
1250
1225
1210
1185
60 h
450
425
410
385
Amount of current from Aux output using a 27Ah battery (SPC535x/635x)
COMMS
NONE (mA)
PSTN (mA)
GSM (mA)
PSTN+GSM (mA)
Standby time
12 h
1900
1875
1860
1835
24 h
775
750
735
710
30 h
550
525
510
485
60 h
100
75
60
35
Amount of current from Aux output using two 27Ah batteries (SPC535x/635x)
COMMS
NONE (mA)
PSTN (mA)
GSM (mA)
PSTN+GSM (mA)
Standby time
12 h
2205
2180
2165
2140
24 h
1900
1875
1860
1835
30 h
1450
1425
1410
1385
60 h
550
525
510
485
Values listed as N/A indicate that the selected battery does not have the capacity to power the minimum
load of just the SPC controller for the given standby time. See
Calculating the battery power requirements
on page 364 for maximum load of devices and modules.
Only sealed cell valve regulated battery types to be used.
For EN compliance the supplied current needs to be supported by the battery for required stand by
time.
23.5 Domestic, Commercial and Financial mode default settings
This table gives the default zone name and types on the controller for each mode of operation. All zones on connected
expanders are be categorized as unused until explicitly configured by the installation engineer.
Feature
Domestic mode
Commercial mode
Financial mode
Zone Names
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Appendix
© Vanderbilt 2018
366
A6V10276959-d
11.2018
Содержание SPC4 Series
Страница 1: ...SPC4xxx 5xxx 6xxx Installation Configuration Manual Document ID A6V10276959 d Edition date 11 2018 ...
Страница 400: ...24 Notes Vanderbilt 2018 400 A6V10276959 d 11 2018 ...
Страница 401: ...SPC4xxx 5xxx 6xxx Installation Configuration Manual Vanderbilt 2018 401 A6V10276959 d 11 2018 ...