The number of online zones is displayed.
5. Press BACK to exit.
16.6.4 Keypads/Expanders/Door Controllers
16.6.4.1 Locate
To locate a keypad/expander/door controller:
1. Scroll to KEYPADS, EXPANDER or DOOR CONTROLLER and press SELECT.
2. Scroll to LOCATE and press SELECT.
3. Scroll to the expander/keypad/door controller to be located and press SELECT.
The selected device beeps and the LED flashes allowing Engineer to locate it.
4. Press BACK to exit.
Locate keypads using the same menus and following the keypad choice instead of expander.
16.6.4.2 Monitor
To obtain an overview of the keypads/expanders/door controller connected to the system:
1. Scroll to KEYPADS, EXPANDER or DOOR CONTROLLER and press SELECT.
2. Scroll to MONITOR and press SELECT.
3. Scroll to desired Monitor programming option.
4. Press SELECT.
A list of detected keypads/expanders is displayed.
5. Scroll through the list and press SELECT on preferred expander/keypad/door controller.
Parameters and details, if applicable, are displayed for editing as shown in the table below.
STATUS
Online or offline
S/N
Serial number (used to track and identify)
VER
Firmware version
POWER
Power parameters: real-time voltage and current readings
ADDRESS
INFO
The addressing mode and the address of the keypad/expander/door controller.
AUX FUSE The status of the auxiliary fuse on the expander/door controller
PSU
The type and status of the PSU. (PSU expanders only) Scroll to display the
voltage and current load on the outputs, the battery status. The Mode Link option
is also available, which shows the jumper setting on the panel for the Ah setting.
7Ah and 17Ah are the available options. (This jumper is not present on the 5350
or 6350 models)
If you are using the SPC 5360 or 6350, this menu displays the battery status, and
the status of the fuses on the outputs.
BATTERY
Battery voltage: battery voltage level (PSU expanders only)
INPUT
STATE
State of each zone input associated with an expander as follows:
C: Closed, O: Open, D; Disconnected, S: Short (Expanders with inputs only)
6. Press BACK to exit.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Engineer programming via the keypad