Restriction
System
Option
Description
Antimask
Unset
Select the type of event reported resulting from antimask detection when panel
is Unset. Options are Disabled, Tamper, Trouble or Alarm.
The option can only be configured when the panel is in ‘Unrestricted’ mode. In
Grade 2 or 3 mode, the type of event reported is in accordance with the
standards for the selected region:
l
Ireland - Disabled
l
All other regions - Tamper
Out of bounds
EOL unset
Select the type of event reported resulting from Out of Bounds EOL detection
when the panel is unset. Options are: Disabled, Tamper and Trouble.
The option can only be configured when the panel is in ‘Unrestricted’ mode. In
Grade 2 or 3 mode, the type of event reported is in accordance with the
standards for the selected region:
l
Germany VDS – Tamper
l
All other regions - Trouble
Out of bounds
EOL set
Select the type of event reported resulting from Out of Bounds EOL detection
when the panel is set. Options are: Disabled, Tamper and Trouble.
The option can only be configured when the panel is in ‘Unrestricted’ mode. In
Grade 2 or 3 mode, the type of event reported is in accordance with the
standards for the selected region:
l
Germany VDS – Tamper
l
All other regions – Trouble
Zone Unstable
unset
Select the type of event reported resulting from Zone Unstable detection when
the panel is unset. Options are: Disabled, Tamper and Trouble.
A zone is unstable if a valid sample cannot be obtained within 10 seconds.
The option can only be configured when the panel is in ‘Unrestricted’ mode. In
Grade 2 or 3 mode, the type of event reported is in accordance with the
standards for the selected region:
l
Germany VDS – Tamper
l
All other regions – Trouble
Zone Unstable
set
Select the type of event reported resulting from Zone Unstable detection when
the panel is set. Options are: Disabled, Tamper and Trouble.
A zone is unstable if a valid sample cannot be obtained within 10 seconds.
The option can only be configured when the panel is in ‘Unrestricted’ mode. In
Grade 2 or 3 mode, the type of event reported is in accordance with the
standards for the selected region:
l
Germany VDS – Tamper
l
All other regions – Trouble
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Engineer programming via the browser
© Vanderbilt 2018
255
A6V10276959-d
11.2018