See
on page 379 and
WARNING: Your attention is drawn to the fact that by allowing this method of unsetting, if an
intruder succeeds in forcing the initial entry door, the police will not be called, regardless of the
intruder’s further progress through the premises.
This method of unsetting the intruder alarm system might be unacceptable to your insurers.
6.4.6 Unsetting in conjunction with an alarm receiving centre (ARC)
Compliance by SPC using third party ARC software. Indication external to the building must be
provided by means of a timed buzzer/strobe, etc., that will operate on a system unset for a timed
period, for example, 30 seconds.
See
3.5.4 Configuration requirements for PD 6662:2010 conformance
Recommendations for the recording of remotely notified alarm conditions (BS 8243:2010 -
Annex G.1 and G.2)
Alarm conditions can be categorised for analysis in accordance with Annex G if the SPC system is
configured so that the entry timer is less than 30 seconds, and the dialer delay is set to 30 seconds.
See the following sections:
l
l
l
Requirements for systems using dedicated alarm paths (BS EN 50136-1-2, 1998)
The SPC system should be configured to do an automated test call to the ARC.
The SPC system should be configured with a 'Fail to Communicate‘ output.
See the following section:
l
Adding/Editing an ARC using SIA or CID
Requirements for equipment used in systems with digital communicators using PSTN (BS EN
50136-2-2, 1998)
Fault Output
The SPC system should be configured with a 'Fail to Communicate‘ output.
See the following sections:
l
on page 152 (Keypad)
l
Configuring controller inputs and outputs
on page 229 (Browser)
l
Adding/Editing an ARC using SIA or CID
Retransmission Attempts
Retransmission attempts (Dial Attempts) are configured in this manual:
l
Adding/Editing an ARC using SIA or CID
l
A minimum of 1 and a maximum of 12 retransmissions are allowed.
Intrusion and hold-up - System design (DD CLC TS 50131-7, 2008)
Setting and unsetting
SPC system is configurable in such a way that the setting is completed by 'Final Exit'.
It is possible to configure the SPC so that a WD (Warning Device) is activated momentarily on setting.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Directives and standards
© Vanderbilt 2018
26
A6V10276959-d
11.2018