Attribute
Description
Prevent
Passback*
Anti-passback should be enforced on the door. All doors must have entry and exit readers and
must be assigned to a door group.
In this mode, cardholders must use their access card to gain entry into and exit from a defined
door group. If a valid cardholder has presented his access card to enter a door group and not
presented the card to exit it, the cardholder is in breach of the anti-passback rules. Next time the
cardholder attempts to enter the same door group, a hard anti-passback alarm will be raised and
the cardholder will not be permitted entry to the door group.
Soft
Passback*
Anti-passback violations are only logged. All doors must have entry and exit readers and must be
assigned to a door group.
In this mode, cardholders must use their access card to gain entry to and exit from a defined door
group. If a valid cardholder has presented his access card to enter a door group and not presented
the card to exit it, the cardholder is in breach of the anti-passback rules. Next time the cardholder
attempts to enter the same door group, a soft anti-passback alarm will be raised. However, the
cardholder will still be permitted entry to the door group.
Custodian*
The custodian feature allows a card holder with custodian right (the custodian) to give other
cardholders (non-custodians) access to the room.
The custodian must be the first to enter the room. The non-custodians are only allowed to enter if
the custodian is in the room. The custodian will not be allowed to exit until all non-custodians have
left the room.
Door
Sounder
Door controller PCB mounted sounder sounds on door alarms.
Ignore
Forced
Door forced open is not processed.
Interlock*
(Browser)
Only one door in an area will be allowed open at a time. Requires Door Group.
Setting
Prefix
Authorisation with prefix (A,B,* or #) key to set system
* Require door group
Door timers
Timer
Min.
Max.
Description
Access
granted
1 s
255 s
The time the lock will remain open after granting access.
Access
deny
1 s
255 s
The duration after which the controller will be ready to read the next event after a
invalid event.
Door open
1 s
255 s
Duration within which the door must be closed to prevent a “door open too long”
alarm.
Door left
open
1
min
180
min
Duration within which the door must be closed to prevent a “door left open” alarm.
Extended
1 s
255 s
Additional time after granting access to a card with extended time attribute.
Escort
1 s
30 s
Time period after presenting a card with escort attribute within a user without escort
right can access the door.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Engineer programming via the browser
© Vanderbilt 2018
281
A6V10276959-d
11.2018
Содержание SPC4 Series
Страница 1: ...SPC4xxx 5xxx 6xxx Installation Configuration Manual Document ID A6V10276959 d Edition date 11 2018 ...
Страница 400: ...24 Notes Vanderbilt 2018 400 A6V10276959 d 11 2018 ...
Страница 401: ...SPC4xxx 5xxx 6xxx Installation Configuration Manual Vanderbilt 2018 401 A6V10276959 d 11 2018 ...