3.2.1 Compliance with EN50131 Approvals
Software Requirements
l
In the
Standards
settings page, select
Europe
under
Region
to implement EN50131
requirements.
l
Select
Grade 2
or
Grade 3
to implement the grade of EN50131 compliance.
l
The
Wireless
setting
Prevent Setting Time
must be set to a value greater than 0 and less than
20.
l
The
Wireless
setting
Device Lost Time
must be set to a value less than 120.
l
The
X-BUS Settings, Retries
, must be set to a value of 10.
l
The
X-BUS Settings, Comms timer
, must be set to a value of 5.
l
Select
Synchronization Time with Mains
under
Clock
settings to use mains as clock master.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual
Directives and standards
© Vanderbilt 2018
20
A6V10276959-d
11.2018