Technical data 11
Operating manual VRC 630 0020095108_00
47
11.2
Default settings
The default settings can only be set, and if necessary
reset, in the Installer level.
Displayed text
Adjustable parameters
Setting range
Default setting
Heating circuit parameters
Night set back temp
Max limit outs.temp.
Pump delay time
Minimum temperature
Maximum temperature
Max. advanced heating time
Switch-on room temperature
Fixed value day
Fixed value night
Max limit outs.temp.
Return temperature
5 - 30 °C
5 - 50 °C
0 - 30 min
15 - 90 °C
15 - 90 °C
0 - 300 min
none/room temp./thermostat
5 - 90 °C
5 - 90 °C
5 - 50 °C
15 - 60 °C
15 °C
21°C
0 min
15 °C
75 °C / 90 °C
0 min
n/a
65°C
65°C
21°C
30°C
Cylinder charging circuit parameters
Charging pump overrun
Anti-legionella function
Legionella protect - start
Parallel charging
0 - 15 min
Off, Mon, Tue, ...Sun, Mon-Sun
00:00 – 24:00
Off/On
5 min
Off
04:00
Off
Overall system parameters
Max. pre-switch off
Frost protection delay
Continuous heating
Fast temperature increase
0 - 120 min
0 - 23 h
Off, -25 ... 10°C
0 - 15 K
15 min
1 h
Off
0 K
Heating appliance parameters
Switching hysteresis
Minimum temperature
Cylinder starting output
1 – 20 K
15 - 90 °C
1 - 2
8 K
15 °C
1
Heating appliance: Cascade parame-
ters
(only for cascade systems)
Switch on delay
Switch off delay
Reverse boiler sequence
1 - 90 min
1 - 90 min
Off/On
5 min
5 min
Off
Special function - teleSWITCH
teleSWITCH for heat zone 1
teleSWITCH for heat zone 2
teleSWITCH for cylinder
None, heating, off, Auto, Eco, Energy sav
None, heating, off, Auto, Eco, Energy sav
None, On, Off, Auto
Energy sav.
Energy sav.
Off
Special function - floor drying
heat zone 2 schedule
heat zone 3 schedule
0 - 29
0 - 29
0
0
Service
Telephone number of expert techni-
cian
Maintenance date
Temp. fault detection after
0 - 9 (17 digit)
Date
OFF, 0 - 12 h
-
01.01.01
Off
Tool
Temperature correction:
Outside temperature
Current room temperature
Display contrast
-5 ... +5 K
-3 ... +3 K
0 - 15
0 K
0 K
11
Table 11.2 Default settings