Installation Instructions VRC 630 0020095108_00
7 Operating the controller
7.4.4 Menu A6: Setting the type of use
In Menu
A6
, all the connected heating circuits can be
configured according to how they are used.
Installation Assistant
A6
System configuration
HK1
Direct circuit
HK2
Mixer circuit
HK3
Mixer circuit
Cylinder
Cylinder charge
>Select
Settable
parameters
Description
Setting range
Factory setting
HK1
Type of use for HK1
–
Direct circuit, disabled
Direct circuit
HK2 ... HK15
Type of use
for HK2 ... HK15
–
Direct circuit or mixer circuit/
fixed value/return flow boost/
Cylinder charging circuit/disabled
Mixer circuit
Cylinder
Type of use for cylinders
–
Cylinder charging circuit, disabled
Cylinder charging
circuit
Table 7.24 Settable parameters in Menu A6
Depending on the type of use for the heating circuits,
only the values and parameters that are of significance
for the selected circuit type will be displayed in the
menus.
The following settings are possible for mixer circuits:
Mixer circuit
:
Underfloor or radiator circuit as a mixer circuit,
Fixed value
:
Mixer circuit is controlled at a fixed value,
Return flow boost
:
to protect against corrosion in the heating boiler
caused by prolonged periods below the dew point (for
conventional heating appliances and systems with
large water capacities),
Cylinder charging circuit:
Control of an additional DHW cylinder
disabled:
when this circuit is not being used.
blanks the parameters for the circuit
no target flow temperature is determined for the
circuit.
–
–
–
–
–
–
–