75
Installation Instructions VRC 630 0020095108_00
Operating the controller 7
7.4.3 Menu A5: Setting priority and cascade
parameters
In Menu
A5
you determine whether hot water genera-
tion or heating has priority.
Installation Assistant
A5
System configuration
Preference
No
>Select
Settable
parameters
Description
Setting
range
Factory
setting
Preference
Preference
works like an isolating circuit for an individual boiler.
The cylinder is directly connected hydraulically to the boiler.
In the case of an individual boiler, the cylinder can also be directly
connected hydraulically to the boiler. Cylinder charging has priority
over heating; the requirements of the heating circuits cannot be
covered at this time. During cylinder charging, the internal 3-way
valve or the charging pump in the boiler is activated. This parameter
only appears if no cascade has been detected.
Yes/No
No
Stop valve
A low-loss header is not needed for boilers with a large water capa-
city. In cascades, the boilers that are not active are isolated from
the active boilers by means of a stop valve. The valve is connected
to the boiler pump in the boiler electronics. The valve in the lead
boiler will always be activated in this case, as otherwise the heat
consumer pumps will be working against the pumps.
Yes/No
No
Isolation switch
Is set to
YES
if in a cascade the cylinder is directly connected
hydraulically to the last boiler in the cascade and not to the collec-
tor downstream of the low-loss header. The unit is then "isolated"
from the cascade during cylinder charging and charges the cylinder,
while the remaining units in the cascade can continue to service the
heating circuits. During cylinder charging, the internal 3-way valve
or the charging pump in the boiler is activated. This parameter only
appears with a cascade.
Yes/No
No
Reverse boiler
sequence
When several boilers of the same type are cascaded, the operating
times of the units should be evenly distributed by means of this
function. The controller sums the time for which it has activated
each boiler (the activation hours). Daily at midnight the controller
checks whether the difference in activation hours > 100 and re-sorts
the boilers if this is the case.
ON/OFF
Off
Table 7.23 Settable parameters in Menu A5
Set the parameters according to the heating installa-
tion.
>
With cascades the display shows the following parame-
ters:
Installation Assistant
A5
System configuration
Stop valve
No
Isolation switch
No
Reverse boiler sequence
Off
>Select
Содержание VRC 630
Страница 1: ...GB VRC 630 3 ...
Страница 2: ......
Страница 54: ......
Страница 55: ...For the heating engineer Installation Manual VRC 630 ...
Страница 145: ...91 Installation Instructions VRC 630 0020095108_00 Appendix Declaration of conformity Fig A 1 Declaration of conformity ...
Страница 152: ...0020095108_00 GB 022010 Subject to alterations ...