Installation Instructions VRC 630 0020095108_00
Operating the controller 7
Settable
parameters
Description
Setting range
Factory
setting
Anti-legionella
function
The anti-Legionella function can only be activated globally for all
cylinder charging circuits.
When the anti-Legionella function is enabled, the respective cylin-
der and the corresponding hot water pipes are heated up to a
temperature of 70 °C at the set time. To this end the respective
target cylinder temperature is automatically raised to 70 °C (with
5 K hysteresis). The corresponding circulation pump is switched
on.
The function is terminated automatically when the cylinder sensor
measures a temperature
≥
60 °C for longer than 60 mins, or after
a period of 90 mins has elapsed (to avoid getting “stuck“ in this
function if water is drawn simultaneously).
Default setting =
Off
means:
no anti-Legionella function (due to danger of scalding).
–
–
–
Off, Mon,
Tue, Wed,
Thu, Fri, Sat,
Sun, Mon-
Sun
Off
Legionella protect
- start
The anti-Legionella function starts automatically when the set
time is reached.
Agree with the owner a suitable time for the anti-Legionella func-
tion, to avoid scalding.
–
>
00:00 ...
23:50
4:00
Table 7.12 Settable parameters in Menu C4 (continued)