73
Installation Instructions VRC 630 0020095108_00
Operating the controller 7
7.3.8 Menu C12: Setting the temperature correction
and the display contrast
In Menu
C12
you optimise the display of temperatures
and the display contrast.
Tool
C12
Temperature correction
Outside temperature
0.0 K
Current room tempe-
rature
0.0 K
Display contrast
11
Settable
parameters
Description
Setting range
Factory
setting
Outside temperature
Correction value for the measured outside temperature
–
-5.0 ... +5.0 K 0.0 K
Current room tempe-
rature
Correction value for the measured room temperature
–
-3.0 ... +3.0 K 0.0 K
Display contrast
Adjustable contrast for good legibility
–
0 ... 15
11
Table 7.21 Settable parameters in Menu C12
If there is a constant difference between the displayed
and the actually measured temperature because of the
installation location, this deviation can be compensated
for by using the correction value.
Example using outside temperature:
Outside temperature displayed on the controller: +5°C;
Measured outside temperature:
+ 7°C;
Set the correction value +2.0 K.
Proceed in the same way for deviations between the
actually measured and the displayed room tempera-
ture.
7.3.9 Menu C15: Checking software versions
Menu C12 is an information menu in which the software
versions of the I/O card and the User Interface are dis-
played.
Entries are not possible. The version numbers are auto-
matically detected and displayed during commissioning.
Software versions
C15
I/O card
2
4.23
User Interface
1
4.27
Menus
A1
to
A7
of the Installation Assistant are con-
nected to Menu
C12
.
>
>
Содержание VRC 630
Страница 1: ...GB VRC 630 3 ...
Страница 2: ......
Страница 54: ......
Страница 55: ...For the heating engineer Installation Manual VRC 630 ...
Страница 145: ...91 Installation Instructions VRC 630 0020095108_00 Appendix Declaration of conformity Fig A 1 Declaration of conformity ...
Страница 152: ...0020095108_00 GB 022010 Subject to alterations ...