74
Installation Instructions VRC 630 0020095108_00
7 Operating the controller
7.4 Parameters
in
the
Installation Assistant
Menus
A1
...
A7
of the Installation Assistant are located
in the Installer level behind Menu
C15
and can also be
called up at any time after the initial start-up.
Check the presets in Menus
A1
...
A7
of the Installation Assistant diligently.
7.4.1
Menu A1: Setting the language
The language for the menu texts is set in this menu.
Installation Assistant
A1
Language selection
Language
EN English
>Select language
Set the language.
7.4.2 Menu A4: Configuring boilers
You configure the heating installation in Menu
A4
.
If the automatic system configuration does not detect
the connected heating appliances and
the number of stages in a cascade system
then set the parameters in Menu
A4
manually.
Installation Assistant
A4
System configuration
Number of boilers
1
Appliance are
modulated
Boilers on
7-8-9
>Select
Settable
parameters
Description
Setting range
Factory set-
ting
Number of boilers
Number of boilers (can be set if no bus coupler or directly
connected eBUS boiler has been detected)
–
1 or 2
1
Boilers are
Boilers are (only if boilers which are activated in stages have
been detected: e.g via a VR 31 or
eBUS boilers)
–
1-stage or
2-stage
1-stage
Boilers on
Boilers on (only appears if no bus coupler or directly con-
nected eBUS boiler has been detected)
–
Stage 1-2 or
7, 8, 9
7, 8, 9
Table 7.22 Settable parameters in Menu A4
>
>
–
–
Содержание VRC 630
Страница 1: ...GB VRC 630 3 ...
Страница 2: ......
Страница 54: ......
Страница 55: ...For the heating engineer Installation Manual VRC 630 ...
Страница 145: ...91 Installation Instructions VRC 630 0020095108_00 Appendix Declaration of conformity Fig A 1 Declaration of conformity ...
Страница 152: ...0020095108_00 GB 022010 Subject to alterations ...