Protecting from Legionella
The controller is furnished with an anti-Legionella func-
tion to protect from infection by germs (Legionella).
Set the anti-Legionella function when installing the
controller.
Preventing the risk of scalding
There is a danger of scalding at the hot water draw-off
points when the target temperatures are in excess of
60 °C. Young children and elderly persons are particu-
larly at risk, even at lower temperatures.
Select a moderate target temperature.
When the anti-Legionella function is active, the DHW
cylinder is heated to over 65 °C for at least one hour.
Inform the owner about the risk of scalding when the
anti-Legionella function is active.
Protecting the controller from damage
Make sure that the controller is protected from mois-
ture and water splashes.
Avoiding malfunctions
To avoid malfunctions, take care that
the heating installation is only operated in a tech-
nically perfect condition,
no safety or monitoring devices have been remo-
ved, bridged out or disabled,
faults and damage that affect safety are rectified
immediately.
Make the owner aware that
the controller must not be obstructed by furniture,
curtains or other objects if it is installed in the
living room,
all the radiator valves in the room where the con-
troller is installed must be turned fully open.
Preventing frost damage
If there is a power cut or if the room temperature is set
too low in individual rooms it can not be ruled out that
sections of the heating system are damaged by frost.
Inform the owner as to how to ensure protection
from frost.
>
>
>
>
>
–
–
–
>
–
–
>
2.4
Directives, laws and standards
EN 60335–2–21
Safety of household and similar electrical appliances;
Part 2: Particular requirements for storage water hea-
ters (domestic hot water cylinders and hot water boi-
lers)
(IEC 335–2–21: 1989 and supplements 1; 1990 and 2;
1990, modified)
Any telecommunications equipment connected must
conform to the following standards: IEC 62151, or
EN 41003 and EN 60950-1: 2006 Section 6.3.
When carrying out the electrical installation, observe
the regulations of the German electrical engineering
association (VDE) and your power supply company
(EVU).
Use standard commercial cables for wiring.
Minimum cross-section of the conductors:
230 V supply cable, rigid conductor
(pump or mixer connecting cable):
1.5 mm
2
Low-voltage conductors
(sensor or bus lines):
0.75 mm
2
The following maximum cable lengths must not be
exceeded:
Sensor lines:
50 m
Bus lines:
300m
At lengths of over 10 m, 230V supply cables must be
laid separately from sensor or bus lines.
Fasten the supply cables using the cable clamps in
the wall mount.
Do not use the free terminals in the unit as supports
for other wiring.
The controller should only be installed in dry rooms.
All wiring must be in accordance with Building Regulati-
ons Part P and BS 7671 (IEE Wiring Regulations), and
must be carried out by a suitably qualified person.
>
>
–
–
–
–
>
>
>
>
7
Installation Instructions VRC 630 0020095108_00
Safety instructions and regulations 2
Содержание VRC 630
Страница 1: ...GB VRC 630 3 ...
Страница 2: ......
Страница 54: ......
Страница 55: ...For the heating engineer Installation Manual VRC 630 ...
Страница 145: ...91 Installation Instructions VRC 630 0020095108_00 Appendix Declaration of conformity Fig A 1 Declaration of conformity ...
Страница 152: ...0020095108_00 GB 022010 Subject to alterations ...