114
1~32
0x10
0x00
0x1E
0x00
0x01
0x02
0~999
High
8-bit
0~999
Low
8-bit
Calculated based
on the first 9
bytes
3)
Return Instruction Format
6.4.2.30
Address 31 (Setting Voltage)
1)
Command Description
This command is used to set the set voltage value in the programmed mode. The command data range is
0.0~300.0V.
2)
Send Instruction Format
Instrument
address
Function
code
High
address
Low
address
High
bytes
Low
bytes
Number
of data
Data byte 1~4
CRC
Low
CRC
High
1~32
0x10
0x00
0x1F
0x00
0x02
0x04
0.0~300.0V, 4
bytes stored in
float point type
Calculated based on
the first 11 bytes
3)
Return Instruction Format
6.4.2.31
Address 32 (Voltage Mode)
1)
Command Description
This command is used to set the voltage output mode in manual mode. Instruction data byte bit
corresponds to instrument voltage output mode as shown in below table:
Data Byte
Instrument voltage output mode function
0x00
This command is used to set the voltage output in manual mode to AUTO mode.
0x01
This command is used to set the voltage output in manual mode to HIGH mode.
2)
Send Instruction Format
Instrument
address
Function
Code
High Address
Low Address
High bytes
Low bytes
CRC Low
CRC High
1~32
0x10
0x00
0x1E
0x00
0x01
Calculated based on the first 6
bytes
Instrument
address
Function
Code
High Address
Low Address
High bytes
Low bytes
CRC Low
CRC High
1~32
0x10
0x00
0x1F
0x00
0x02
Calculated based on the first 6
bytes