12-2
12.3 Application errors
When the problem about application happens, please confirm that is shown in the following table and
take measures. If the problem does not improve, please contact us.
Table 12.3.1 Application errors
Trouble Factor
Measure
Measurement value is
incorrect.
Settings for the
installation is incorrect.
・
Please check setting G, R, C, H, the tank
shape and so on are correct. (Refer to
6.3
Settings
)
・
If correction values (the offset value slope)
are set, please check that are correct.
(Refer to
6.3 Settings
)
・
Please check the using antenna shape is
equal to the configuring antenna shape.
May have to measure
the reflected waves due
to noise..
・
Please make the appropriate adjustment,
refer to the echo curve.
(
Refer to
6.6
Advanced settings
and
6.8 Echo Viewer
)
・
There is a possibility of the reflected wave
from the antenna contaminations. Please
wash of the antenna.
・
There is a possibility of the reflected wave
from the surrounding structure. Please take
change oscillation direction or mounting
position.
(
Refer to
2.2 Appropriate location
for installation
or
2.7 Tips for stable
measurement
)
・
Please try to set the outlier removal. (Refer
to
6.6.2 Outlier Removal
)
May have to measure
the reflected wave by
double bounce.
・
Please make the appropriate adjustment,
refer to the echo curve.
(
Refer to
6.6
Advanced settings
and
6.8 Echo Viewer
)
・
Please try to set the outlier removal. (Refer
to
6.6.2 Outlier Removal
)
It does not follow the
variation of the level.
May have to measure
the reflected waves due
to noise.
・
Please make the appropriate adjustment,
refer to the echo curve.
(
Refer to
6.6
Advanced settings
and
6.8 Echo Viewer
)
・
There is a possibility of the reflected wave
from the antenna contaminations. Please
wash of the antenna.
・
Please try to set the outlier removal. (Refer
to
6.6.2 Outlier Removal
)
Содержание KRG-10
Страница 1: ...Document No KF13 001K Microwave Level Gauge RG 10 User s Guide...
Страница 9: ...8 Blank...
Страница 13: ...12 Blank...
Страница 17: ...1 4 Fig 1 2 4 Transmitter head with rod antenna 1 Transmitter head 2 Flange option 3 1 rod antenna...
Страница 51: ...3 8 Blank...
Страница 55: ...4 4 Blank...
Страница 171: ...9 2 Blank...
Страница 181: ...10 10 10 4 Optional specifications Table 10 4 1 Optional specifications CD R Configuration software...
Страница 190: ...10 19 M20 1 5 Fig 10 7 6 Cable gland Only Non Ex type...
Страница 193: ...11 2 Blank...
Страница 197: ...12 4 Blank...
Страница 199: ...Blank...