12-3
If the liquid surface is
rough, measurement
value shows a high
value instantaneous.
Since the microwave
signal is weakened
temporarily for the rough
surface, noise reflection
becomes stronger.
・
Please make the appropriate adjustment,
refer to the echo curve.
(
Refer to
6.6
Advanced settings
and
6.8 Echo Viewer
)
・
Please optimize the mounting position and
oscillation direction. (
2.2 Appropriate
location for installation
)
・
Please change to a large size antenna.
(Because of a large antenna in a high
sensitivity, tend to noise is small relative to
the microwave signal.)
・
Please try to set the outlier removal. (Refer
to
6.6.2 Outlier Removal
)
Measurement
indicates a low value
momentarily.
May have to measure
the reflected waves due
to noise.
・
There is a possibility of the reflected wave
from the surrounding structure. Please take
change oscillation direction or mounting
position.
(
Refer to
2.2 Appropriate location
for installation
or
2.7 Tips for stable
measurement
)
・
There is a possibility of measuring the
short-range noise. Please try widening the
dead band or the setting of the outlier
removal and so on. (Refer to
6.6 Advanced
settings
and
6.8 Echo Viewer
)
Содержание KRG-10
Страница 1: ...Document No KF13 001K Microwave Level Gauge RG 10 User s Guide...
Страница 9: ...8 Blank...
Страница 13: ...12 Blank...
Страница 17: ...1 4 Fig 1 2 4 Transmitter head with rod antenna 1 Transmitter head 2 Flange option 3 1 rod antenna...
Страница 51: ...3 8 Blank...
Страница 55: ...4 4 Blank...
Страница 171: ...9 2 Blank...
Страница 181: ...10 10 10 4 Optional specifications Table 10 4 1 Optional specifications CD R Configuration software...
Страница 190: ...10 19 M20 1 5 Fig 10 7 6 Cable gland Only Non Ex type...
Страница 193: ...11 2 Blank...
Страница 197: ...12 4 Blank...
Страница 199: ...Blank...