5-15
[3-4] Minimum Value
Enter the minimum value of analog current output range.
[3-5] Maximum Value
Enter the maximum value of analog current output range.
[3-6] Alarm Output Factor
Enter the factor of alarm output.
0: No Receiving Echo
Select if alarm is output when echo cannot be detected
1: Device Failure
Select if alarm is output when the device failure
2: Both
Select if alarm is output when echo cannot be detected or the device failure
[4-0] Averaging Time
Measuring value is averaged in accordance with [sec] setting.
[4-1] Median Filter
Set allowable value using calculation to get accurate measured value.
Please refer to
6.6.1 Measurement Support
for the details.
[4-2] Re-search Delay
Time delay after loss of surface echo until search in accordance with [sec] setting.
[4-3] Alarm Delay
Time delay after loss of surface echo until alarm signals in accordance with [sec] setting.
[4-4] Surface Detect Mode
Enter the echo detected as the liquid level echo.
0: Max Echo
Max strength echo defined as surface echo
1: First Echo
First echo defined as surface echo
Distance
First Echo
Max Echo
Fig. 5.4.5 Surface Detect Mode
[4-5] Negative Level as Zero
While this function is "On", zero level will be outputted instead of negative level.
0: Off
1: On
Содержание KRG-10
Страница 1: ...Document No KF13 001K Microwave Level Gauge RG 10 User s Guide...
Страница 9: ...8 Blank...
Страница 13: ...12 Blank...
Страница 17: ...1 4 Fig 1 2 4 Transmitter head with rod antenna 1 Transmitter head 2 Flange option 3 1 rod antenna...
Страница 51: ...3 8 Blank...
Страница 55: ...4 4 Blank...
Страница 171: ...9 2 Blank...
Страница 181: ...10 10 10 4 Optional specifications Table 10 4 1 Optional specifications CD R Configuration software...
Страница 190: ...10 19 M20 1 5 Fig 10 7 6 Cable gland Only Non Ex type...
Страница 193: ...11 2 Blank...
Страница 197: ...12 4 Blank...
Страница 199: ...Blank...