6-49
(1) Current Loop Check
To perform a current loop check, select current loop check (
) and then use the "Up" and
"Down" buttons to select the output current value.
Fig. 6.7.12 Output current value setting bar
Then, if you click the "Start" button, the following window will be displayed, so click "OK", and
current loop check will begin.
Fig. 6.7.13 Fixed current output confirmation dialog box
Then the following window will be displayed, so follow the window display to measure the output
current. When measurement has finished, click "OK".
Fig. 6.7.14 Current value measurement instructions dialog box
It is then possible to repeat the next current value measurement in a similar manner by using
the "Up" and "Down" buttons. To finish current loop check, click the "End" button. The current
output value after current loop check has finished returns to the measurement value.
Moves using "Up" and "Down"
buttons