7-3
7.4 Setting volume calculation / flow calculation
(1) Volume calculation
To calculate volume, select a standard tank shape from among those in the "Volume calc. method"
setting parameter (vertical cylindrical shape / spherical shape / horizontal cylindrical shape) or
select a user definition. If you select a standard tank shape, set each of the required parameters.
The standard tank setting parameters are shown in the following table.
Table 7.4.1 Standard tank shape setting parameters
Setting parameter / tank shape
Vertical
cylinder shape
Sphere shape
Horizontal
cylinder shape
A (Maximum Position)
●
●
●
O (Tank offset)
●
●
●
D (Tank diameter)
●
●
●
L (Tank length)
-
-
●
If you select a user definition, you must set volume table.
Figure 7.4.1 Setting volume table
Volume table can be set using the configuration software. Between 2 (minimum) and 100
(maximum) calibration points can be set. If the size of the setting level values is wrong (not in
order of smallest [value]), an device status table error occurs, and functions will not operate. For
details on device status, refer to
5.4 Parameter instructions --> [8-3] Device Status
or
6.10
Tools --> Error
.
Содержание KRG-10
Страница 1: ...Document No KF13 001K Microwave Level Gauge RG 10 User s Guide...
Страница 9: ...8 Blank...
Страница 13: ...12 Blank...
Страница 17: ...1 4 Fig 1 2 4 Transmitter head with rod antenna 1 Transmitter head 2 Flange option 3 1 rod antenna...
Страница 51: ...3 8 Blank...
Страница 55: ...4 4 Blank...
Страница 171: ...9 2 Blank...
Страница 181: ...10 10 10 4 Optional specifications Table 10 4 1 Optional specifications CD R Configuration software...
Страница 190: ...10 19 M20 1 5 Fig 10 7 6 Cable gland Only Non Ex type...
Страница 193: ...11 2 Blank...
Страница 197: ...12 4 Blank...
Страница 199: ...Blank...