3-7
3.5 Cable shielding and grounding
In case of Non-Ex and Ex ia, perform grounding structure.(grounding resistance<100
Ω
) In case of Ex
ia/db and Ex d ia, perform grounding structure.(grounding resistance<10
Ω
)
Grounding terminal is outside of the transmitter and inside of the terminal box, respectively. May use
which grounding terminal.
If screened cable is necessary, connect the cable screen on both ends to ground potential. In the
terminal box, the screen must be connected directly to the internal ground terminal.
WARNING
Ex equipment installation requires connection with the earth line.