
5-14
[2-3] B (Breadth of channel)
Channel width. (Please refer Fig 5.4.3 Weir type)
[2-4] b (Width of weir)
Weir width. (Please refer 2: Edged Square of Fig 5.4.3 Weir type)
[2-5] D (Height of weir edge relative to bottom of channel)
Liquid height from notch end. (Please refer Fig 5.4.3 Weir type)
[2-6]
ν
(Kinematic viscosity of fluid)
Input a value of kinematic viscosity coefficient.
[2-7] Flow Unit
Flow rate unit.
Select unit for flow rate.
0: m
3
/D
1: m
3
/h
2: m
3
/min
3: m
3
/sec
4: US Gallons/D
5: US Gallons/h
6: US Gallons/min
7: US Gallons/sec
8: Barrels/D
9: Barrels/h
10: Barrels/min
11: Barrels/sec
12: Ft
3
/D
13: Ft
3
/h
14: Ft
3
/min
15: Ft
3
/sec
[3-0] Analog Current Output Parameter
Enter the content of parameters output at 4-20mA.
0: Level
1: Distance
2: Volume
3: Flow
4: Sig-Amp
[3-1] Minimum Output
Enter the Analog Current Output value corresponding to 4 mA.
(Level / Distance / Volume / Flow / Sig-Amp)
[3-2] Maximum Output
Enter the Analog Current Output value corresponding to 20 mA.
(Level / Distance / Volume / Flow / Sig-Amp)
[3-3] Alarm Selection
Enter the content of alarm output.
0: High
22 mA alarm output
1: Low
3.6 mA alarm output
2: Hold
Hold last value
Содержание KRG-10
Страница 1: ...Document No KF13 001K Microwave Level Gauge RG 10 User s Guide...
Страница 9: ...8 Blank...
Страница 13: ...12 Blank...
Страница 17: ...1 4 Fig 1 2 4 Transmitter head with rod antenna 1 Transmitter head 2 Flange option 3 1 rod antenna...
Страница 51: ...3 8 Blank...
Страница 55: ...4 4 Blank...
Страница 171: ...9 2 Blank...
Страница 181: ...10 10 10 4 Optional specifications Table 10 4 1 Optional specifications CD R Configuration software...
Страница 190: ...10 19 M20 1 5 Fig 10 7 6 Cable gland Only Non Ex type...
Страница 193: ...11 2 Blank...
Страница 197: ...12 4 Blank...
Страница 199: ...Blank...