Synergy Controller Technical Manual, Revision H
Page 241
Page 241
Description
Command Usages
Command Syntax
Range,
Units
Command
Example
Response Example
Calibration Commands
Channel Offset Calibration
CAL* Set
= CAL* ARG1
-50 to 50 C (-90 to 90 F), -50 to
50%
= CAL1 10.0
OK
CAL* Query
? CAL*
-50 to 50 C (-90 to 90 F), -50 to
50%
? CAL1
10.00
Channel Gain Calibration
GAIN* Set
= GAIN* ARG1
50 - 150%
= GAIN1 90
OK
GAIN* Query
? GAIN*
50 - 150%
? GAIN1
90.00
UUT Sensor Calibration Gain
UUTms_GAIN Set
= UUTms_GAIN ARG1
Range: ARG1 = 80 to 120 %
Range: m = 1 thru 8 (Module)
Range: s = 1 thru 8 (Sensor)
= UUT88_GAIN 100.0
OK
UUTms_GAIN Query
? UUTms_GAIN
Same as Set Command
? UUT88_GAIN
100.0
UUT Sensor Calibration Offset
UUTms_OFFSET Set
= UUTms_OFFSET ARG1
(C) Range ARG1 = -100 to 100 C
(F) Range ARG1 = -180 to 180 F
Range: m = 1 thru 8 (Module)
Range: s = 1 thru 8 (Sensor)
= UUT88_OFFSET 2.0
OK
UUTms_OFFSET Query
? UUTms_OFFSET
Same as Set Command
? UUT88_OFFSET
2.0
High Res Analog Calibration
Gain
HIGH#_GAIN Set
= HIGH#_GAIN ARG1
# - High Res Input number 1 - 6
ARG1:
25-200% Gain
= HIGH1_GAIN 105
OK
HIGH#_GAIN Query
? HIGH#_GAIN
# - High Res Input number 1 - 6
? HIGH1_GAIN
105
High Res Analog Calibration
Offset
HIGH#_OFF Set
= HIGH#_OFF ARG1
# - High Res Input number 1 - 6
ARG1:
-100 to 100 units
= HIGH1_OFF 5
OK
HIGH#_OFF Query
? HIGH#_OFF
# - High Res Input number 1 - 6
? HIGH1_OFF
5
High Res Analog
High Voltage Range
HIGH#_HIGHVOLTS Set
= HIGH#_HIGHVOLTS
ARG1
# - High Res Analog Input number
3 - 6
ARG1:
Upper Volt range of the attached
sensor 0 - 5.25V
= HIGH3_HIGHVOLTS 5
OK
HIGH#_HIGHVOLTS
Query
? HIGH#_HIGHVOLTS
# - High Res Analog Input number
3 - 6
? HIGH3_HIGHVOLTS
5.0
High Resolution Analog
Low Voltage Range
HIGH#_LOWVOLTS Set
= HIGH#_LOWVOLTS
ARG1
# - High Res Analog Input number
3 - 6
ARG1:
Lower Volt range of the attached
sensor 0 - 5.25V
= HIGH3_LOWVOLTS .25
OK
HIGH#_LOWVOLTS
Query
? HIGH#_LOWVOLTS
# - High Res Analog Input number
3 - 6
? HIGH3_LOWVOLTS
.25
High Resolution Analog
High Engineering Units
HIGH#_HIGHEU Set
= HIGH#_HIGHEU ARG1
# - High Res Analog Input number
3 - 6
ARG1:
Upper scaled value of the attached
sensor -500 - 5000 units
= HIGH3_HIGHEU 100
OK
Содержание Synergy Compact
Страница 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Страница 71: ...Synergy Controller Technical Manual Revision H Page 71...
Страница 106: ...Synergy Controller Technical Manual Revision H Page 106...
Страница 123: ...Synergy Controller Technical Manual Revision H Page 123...
Страница 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Страница 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Страница 188: ...Synergy Controller Technical Manual Revision H Page 188...
Страница 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Страница 294: ...Synergy Controller Technical Manual Revision H Page 294...
Страница 312: ...Synergy Controller Technical Manual Revision H Page 312...
Страница 345: ...Synergy Controller Technical Manual Revision H Page 345...
Страница 346: ...Synergy Controller Technical Manual Revision H Page 346...