LEV
2
LEV2 (Logic Event 2) controls the vacuum device. When enabled it activates the vacuum device even
if OT17 is set to Purge.
You may select the LEV 2 method while the chamber is running in manual mode or in the
Add Step
Wizard
using the Setpoint step. To monitor the On/Off state of LEV 2, go to the
Events\Event Output
folder and observe the LED light next to the
LEV 2
label. The light is red when the
LEV 2
is activate,
gray when inactivate. Note that the default LEV 2 setting is always off.
♦
OT11 TPM (Ambient Cooling Time Proportioning vs. On/Off Mode)
The OT11 TPM feature is used to change the Ambient
Cooling Coil control mode. The chamber
defaults to On/Off control mode. When OT11 TPM is selected, the controller switches to the time
proportioning mode.
OT11 TPM can be monitored from within the Event Outputs folder. The setting can also be specified
for each Setpoint step. To monitor the state of the
OT11 TPM
setting, go to the
Events\Event Output
folder and observe the LED indicator next to the OT11 TPM label. The light is red when the time
proportioning mode is active, gray when it is inactive. To change the default
OT11 TPM
setting for
Steady State mode, go to the OT11 folder under
Setup\Special Functions\OT11
and select the desired
default method: On/Off Control Mode or Time Proportioning Control Mode.
11.1.3 Event Output Board Options
Tidal Engineering offers two types of event output boards: standard AC output (TE1151-6), and relay output
(TE1708-6). Each of these connects to the Olympic board or to the 2SM board with a 20 position ribbon
cable. Schematic diagrams and wiring instructions for these are included in the
Triac Output Board, 6 Channel
P/N TE1151-6
•
Control up to twelve (6) 3 Ampere AC loads
•
110 - 220 VAC
•
Each output can also drive an external Triac for
larger loads.
Relay Output Board, 6 Channel
P/N TE1708-6
•
Control up to six (6) 3-Ampere AC loads,
•
110 - 220 VAC.
•
Each output is Form C with both a normally open
and normally closed contact.
Содержание Synergy Compact
Страница 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Страница 71: ...Synergy Controller Technical Manual Revision H Page 71...
Страница 106: ...Synergy Controller Technical Manual Revision H Page 106...
Страница 123: ...Synergy Controller Technical Manual Revision H Page 123...
Страница 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Страница 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Страница 188: ...Synergy Controller Technical Manual Revision H Page 188...
Страница 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Страница 294: ...Synergy Controller Technical Manual Revision H Page 294...
Страница 312: ...Synergy Controller Technical Manual Revision H Page 312...
Страница 345: ...Synergy Controller Technical Manual Revision H Page 345...
Страница 346: ...Synergy Controller Technical Manual Revision H Page 346...