Synergy Controller Technical Manual, Revision H
Page 189
The Pressure display on Channel 2 is in scientific notation as shown below. Note that the Pressure Set Point
has no effect on Thermal Vacuum chambers since pressure is not controlled.
Pressure is recorded in the log file in Torr in scientific notation.
To verify setup and calibration verify the values in the following table.
Output in Torr is 10^((Vhires*2)-n)
n, Altitude Setting
V hi-res Volts DC
Display
12
5.0
1.0e-2
11
5.0
1.0e-1
10
5.0
1.0e-0
12
0.0
1.0e-12
11
0.0
1.0e-11
10
0.0
1.0e-10
12
2.1
1.6e-8
11
2.1
1.6e-7
10
2.1
1.6e-6
22.2 Altitude Chamber Setup
Содержание Synergy Compact
Страница 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Страница 71: ...Synergy Controller Technical Manual Revision H Page 71...
Страница 106: ...Synergy Controller Technical Manual Revision H Page 106...
Страница 123: ...Synergy Controller Technical Manual Revision H Page 123...
Страница 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Страница 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Страница 188: ...Synergy Controller Technical Manual Revision H Page 188...
Страница 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Страница 294: ...Synergy Controller Technical Manual Revision H Page 294...
Страница 312: ...Synergy Controller Technical Manual Revision H Page 312...
Страница 345: ...Synergy Controller Technical Manual Revision H Page 345...
Страница 346: ...Synergy Controller Technical Manual Revision H Page 346...