Quick Start Guide
–
SIREC D300 and D400 Display Recorders
Settings
(Main Menu > Configuration)
1. Connections
D300 Mini rear panel
1) 24VDC Inst. power
2) 24V TXP Supply
3) Common Relay Ouput
4) RS485 connection
5) USB Host
6) Ethernet connection
7) AC supply 100-250VAC
8) CJC Connector
Analogue Input board (4, 6 or 8 channel).
D300 = Slots A & B, D400 = Slots A to F
Analogue Output (2 or 4 channel).
D300 = Slot B only, D400 = Slots E&F
Pulse Input (4 channel).
D300 = Slots A & B, SX/GR Multi = Slots A to F
Relay Alarm (4 or 8 channel).
D300 = Slot G, D400 = Slots G to I
Key: NO = Normally Open, C = Common, NC = Normally Closed,
(2) 24V Transmitter Power Supply connections are made via 2-way
for D300, 2x10-way connectors for SX/GR Multi.
D400 Multi rear panel
2. Setup Menu
Select the Menu button
from the Process Screen
Options
Select Options in Credits menu, tick firmware
options to enable. Go to Finish and Commit
Inputs
All Analogue Inputs default to 12V
Select Input channel
Setup input Type. V, A, Ohms, RT, TC
Select Sample Rate
Select Range / RT / TC Type
Use Back button to return to Setup Menu
Pens
By default Pen 1 display
Analogue Input 1, Pen 2
displays Analogue 2 etc .
Select Pen
Setup Scale
Set Alarms, if required
Setup Logging (required to Log and
Save data in memory)
Use Back button to return to Setup Menu
Localization
Settings for Language and Time Zones, etc.
Back
1
A5E01040171-04; 43-TV-25-39 Iss.4 GLO January 2016 UK
MV, V T/C Passive T/C Active Current
Ohms 4 wire R/T 3 wire R/T 2 wire R/T
Digital Input / Output (8 or 16 channel)
D300= Slot G, D400 = Slots G to I