background image

                  Quick Start Guide 

–   

SIREC D300 and D400 Display Recorders

 

 

 

 

Settings 

(Main Menu > Configuration)

 

 

1. Connections 

D300 Mini rear panel 

1) 24VDC Inst. power 
2) 24V TXP Supply 
3) Common Relay Ouput 
4) RS485 connection 
5) USB Host 
6) Ethernet connection 
7) AC supply 100-250VAC 
8) CJC Connector 

Analogue Input board (4, 6 or 8 channel). 

D300 = Slots A & B, D400 = Slots A to F 

Analogue Output (2 or 4 channel).   

D300 = Slot B only, D400 = Slots E&F 

Pulse Input (4 channel).   

D300 = Slots A & B, SX/GR Multi = Slots A to F 

Relay Alarm (4 or 8 channel).   

D300 = Slot G, D400 = Slots G to I 

Key: NO = Normally Open, C = Common, NC = Normally Closed, 

 

(2) 24V Transmitter Power Supply connections are made via 2-way 
for D300, 2x10-way connectors for SX/GR Multi. 

D400 Multi rear panel 

2. Setup Menu 

Select the Menu button 
from the Process Screen 

Options 

Select Options in Credits menu, tick firmware 
options to enable. Go to Finish and Commit 

Inputs 

All Analogue Inputs default to 12V 

Select Input channel 

  Setup input Type. V, A, Ohms, RT, TC 

  Select Sample Rate 

  Select Range / RT / TC Type 

Use Back button to return to Setup Menu 

Pens 

By default Pen 1 display 
Analogue Input 1, Pen 2 
displays Analogue 2 etc . 

Select Pen 

  Setup Scale 

  Set Alarms, if required 

  Setup Logging (required to Log and 

Save data in memory) 

Use Back button to return to Setup Menu 

Localization 

Settings for Language and Time Zones, etc. 

Back 

 

 

 

 

 

 

 

A5E01040171-04; 43-TV-25-39 Iss.4 GLO January 2016 UK 

                MV, V            T/C Passive          T/C Active          Current 

              Ohms              4 wire R/T            3 wire R/T          2 wire R/T 

Digital Input / Output (8 or 16 channel)   

D300= Slot G, D400 = Slots G to I 

Отзывы: