Synergy Controller Technical Manual, Revision H
Page 225
For example, RTD inputs are calibrated in the Setup\Calibration\Input screen in units of Ohms as shown
below:
16.4 End to End Calibration
For End-to-End temperature Calibration, a reference temperature reading is compared against the Synergy
Controller reading. This takes into account and corrects for both sensor and controller characteristics.
The same two point calibration formulas work for End to End Calibration.