Synergy Controller Technical Manual, Revision H
Page 197
PID Heat
Time Proportioning output that controls the heaters.
Output is Time Proportioning
Control Parameters
Default Value:
Range:
Channel 1 Proportional Band
7
0 - 50 Degrees C
Reset for Channel 1 Heating
0.02
0 - 9.9 Repeats/minute
Rate for Channel 1 Heating
0
0 - 9.9 Minutes
Cycle Time for Channel 1 Heating
5
1 - 60 Seconds
Rate Band for Channel 1 Heating
0
0 - 7 Seconds
PID Cool
This is a time proportioning output that energizes the cool solenoid permitting refrigerant flow to the
Evaporator Coil.
Output is Time Proportioning
Control Parameters
Default Value:
Range:
Channel 1 Proportional Band
7
0 - 50 Degrees C
Reset for Channel 1 Cooling
0.02
0 - 9.9 Repeats/minute
Rate for Channel 1 Cooling
0
0 - 9.9 Minutes
Cycle Time for Channel 1 Cooling
5
1 - 60 Seconds
Rate Band for Channel 1 Cooling
0
0 - 7 Seconds
Содержание Synergy Compact
Страница 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Страница 71: ...Synergy Controller Technical Manual Revision H Page 71...
Страница 106: ...Synergy Controller Technical Manual Revision H Page 106...
Страница 123: ...Synergy Controller Technical Manual Revision H Page 123...
Страница 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Страница 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Страница 188: ...Synergy Controller Technical Manual Revision H Page 188...
Страница 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Страница 294: ...Synergy Controller Technical Manual Revision H Page 294...
Страница 312: ...Synergy Controller Technical Manual Revision H Page 312...
Страница 345: ...Synergy Controller Technical Manual Revision H Page 345...
Страница 346: ...Synergy Controller Technical Manual Revision H Page 346...