Synergy Controller Technical Manual, Revision H
Page 207
Dehumidify Coil
This output operates the dehumidify coil for dehumidification.
Output is either Time Proportioning or On/Off
L11 Dehumidify On
Percent dehumidify required to enable dehumidify device
L12 Dehumidify Off
Percent humidity required to turn off dehumidify device
LEV 1
Selects the Drier Device when Input 2 is closed,
otherwise the Dehumidify Coil is selected.
Dehumidify Coil vs. Drier Logic (Input 2)
When closed and when LEV 1 is set to Use Drier,
disables the dehumidify coil and uses the Drier device
instead.
Control Parameters
Default Value:
Range:
Channel 2 Proportional Band Cooling
40
0 - 50 Degrees C
Reset for Channel 2 Cooling
0.1
0 - 9.9 Repeats/minute
Rate for Channel 2 Cooling
0
0 - 9.9 Minutes
Cycle Time for Channel 2 Cooling
7
1 - 60 Seconds
Rate Band for Channel 2 Cooling
0
0 - 7 Seconds
Содержание Synergy Compact
Страница 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Страница 71: ...Synergy Controller Technical Manual Revision H Page 71...
Страница 106: ...Synergy Controller Technical Manual Revision H Page 106...
Страница 123: ...Synergy Controller Technical Manual Revision H Page 123...
Страница 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Страница 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Страница 188: ...Synergy Controller Technical Manual Revision H Page 188...
Страница 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Страница 294: ...Synergy Controller Technical Manual Revision H Page 294...
Страница 312: ...Synergy Controller Technical Manual Revision H Page 312...
Страница 345: ...Synergy Controller Technical Manual Revision H Page 345...
Страница 346: ...Synergy Controller Technical Manual Revision H Page 346...