Appendix A: Specifications, Racking, and Cabling for the V6000 and V6100
Space, Network, and Power Requirements
DSM Installation and Configuration Guide
Copyright 2009 - 2020 Thales Group. All rights reserved.
125
Space, Network, and Power Requirements
Physical dimensions
l
1u, rack-mountable chassis
l
dimensions: 17”x 20-1/2”x 1.75”
External connectors
l
two 10/100/1000baseT network connectors
l
one IPMI connector
l
one DB-9 RS-232 serial console connector
Power requirements
The Vormetric hardware appliance includes two auto-switching, field-replaceable, AC power modules. The power
modules are shipped pre-installed in the Data Security Manager Appliance chassis.
Each power module requires an independent, 100-240V, 47-63Hz, 12V 6A power source.
Peak power consumption on the appliance is 190W.
Power switch and power reset buttons are on the front panel. Power connectors are on the back panel.
Data center environmental requirements
The table below lists the required environmental conditions for the DSM.
Condition
Range
Maximum BTU
410 BTU max
Operating temperature
10° to 35° C (50° to 95° F
Non-operating temperature
-40° to 70° C (-40° to 158° F)
Operating relative humidity
8% to 90% (non-condensing)
Non-operating relative humidity
5% to 90% (non-condensing)
Table A-2: Environmental conditions for the DSM
Appliance Rack Mount Safety Instructions
The only serviceable parts in the Vormetric Data Security Manager Appliance are the power supplies. This unit must
be returned to the manufacturer for replacement of lithium batteries and all other parts.
The following safety conditions must be considered when rack mounting the DSM Appliance:
l
Elevated operating temperature: If the DSM Appliance is installed in a closed or multi-unit rack assembly, the
operating ambient temperature of the rack environment may be greater than the room ambient temperature.
Install the equipment in an environment within the range specified in
"Data center environmental requirements"
.