Controlling with External Analog & Contact Signals
------------------------------------------------------------------------------------
135
Status Output (ZX-S Series Type-HA)
This can externally output the operational status of the ZX-S Series power supply.
Output Circuit
Output is given by a open collector insullated by a photocoupler.
CN1
11
24
12
25
13
26
LEVEL1_ALM
LEVEL2_ALM
CV_STS
CC_STS
P-ON(M)_STS
S-COM
内
部
回
路
Status List
Output signal is negative logic. When output signal is ON between the collector and emitter, logic is 1.
See the following for details on each terminal
’
s signals.
Terminal
Signal Name
Contents
11
LEVEL1_ALM
Light failure (OVP, OCP) has occurred.
24
LEVEL2_ALM
Alarm has occurred.
(Indude Several Alarms)
12
CV_STS
Running in Constant Voltage Mode.
25
CC_STS
Running in Constant Current Mode.
13
P-ON(M)_STS
Internal rectification voltage and power supply for control circuits is
normal.
26
S-COM
Status Common.
Connected to emitters of each photocoupler.
Status Output Electric Specifications
Item
Specifications
Withstand Voltage
DC500V (for DC output-Status Output-Chassis)
Max. Collector Voltage
24V
Max. Collector Current
5mA
Int
ernal
Circ
uits
Содержание ZX-S-H Series
Страница 1: ...Constant Voltage Constant Current DC Power Supply series Instruction Manual ...
Страница 37: ...Basic Operations 33 This is blank page ...
Страница 59: ...Useful Function 55 This is blank page ...
Страница 115: ...Using via Digital Data Communication 111 This is blank page ...
Страница 141: ...Controlling with External Analog Contact Signals 137 This is blank page ...
Страница 147: ...Special Loads 143 This is blank page 守 ...
Страница 188: ... 184 付録 External Diagrams ZX S 400H 400HA 4 M3 ...
Страница 189: ...Appendix 185 ZX S 800H 800HA ...
Страница 190: ...Appendix 186 ZX S 1600H 1600HA ...