ID 442426.04
64
WE KEEP THINGS MOVING
Technical data
4
Manual SD6
4.12.1
Power choke
WARNING!
Risk of burns! Fire hazard! Material damage!
Chokes can heat up to over 100 °C under permitted operating conditions.
Take protective measures against accidental and intentional contact with
the choke.
Make sure that no flammable material is in the vicinity of the choke.
Do not install chokes under or near the drive controller.
WARNING!
Fire hazard!
Using chokes outside of the nominal data (cable length, current, frequency,
etc.) can cause the chokes to overheat.
Always comply with the maximum nominal data when operating the
chokes.
Type
TEP4010-2US00
ID no.
56528
Phases
3
Permitted thermal continuous current
100 A
Rated current
90 A
Rated inductance
0.1410 mH
Mains voltage
480 V
Voltage drop (Uk)
2 %
Frequency
60 Hz
Protection class
IP 00
Max. surrounding temperature
ϑ
amb,max
40° C
Insulation class
B
Connection
Flange connection
Mounting
Screws
Specification
EN 61558-2-20
UL Recognized Component (CAN; USA)
Yes
CE mark
Yes
Identification/test mark, symbol
,
,