Drive controller
9
Manual SD6
9.5.3.2
42:TempBrakeRes
Triggering
Level
Response
Counter
The i
2
t model for the braking resistor exceeds
100% load.
Fault
Parameterized fault response in
A29
:
•
A29 = 0:inactive
The power board is switched off and the drive
becomes torque-free/force-free. If the air override is
inactive, a possibly existing brake will be controlled to
close.
•
A29 = 1:active
The drive is stopped with a quick stop. If the air
override is inactive, a possibly existing brake will be
controlled to close at the end of the quick stop.
Up to firmware V 6.0-F the brake chopper is switched off.
Z42
Possible cause
Test
Measure
Confirmable
The braking resistor may not be
designed according to the
application.
Check whether the load state of the braking
resistor has caused overheating.
Check the drive configuration. Consider a
DC link connection or the use of a braking
resistor with a larger power rating.
Yes