16.47 84:Drop in network with power stage active
Triggering
Level
Response
Counter
A problem was discovered with the supply voltage. Fault
The power board is switched off and the drive becomes
torque-free/force-free unless emergency braking
U30
(
A29
) is parameterized. If the air override is inactive, a
possibly existing brake will be controlled to close.
Z84
Possible cause
Test
Measure
Confirmable
Drop in network
If the mains monitoring detects that the
mains is missing, the load relay is
immediately switched off. Normal operation
is maintained. If the mains return of the
power board is still switched on, a fault is
triggered after 0.5 s.
Check whether the mains voltage
corresponds to the specification or whether
there is a power failure.
Yes