ID 442426.04
100
WE KEEP THINGS MOVING
Connection
7
Manual SD6
Connection without output derater
Observe the following points when connecting the motor without the output
derater:
•
Ground the shield of the motor cable with the shield connection clamp on
the EMC shroud.
•
Keep the exposed conductor as short as possible. All devices and circuits
that are sensitive to EMC must be kept at a distance of at least 0.3 m.
Connection with output derater
Observe the following points when connecting the motor to the output derater:
•
Ground the shield of the motor cable with large area contacts in the
immediate vicinity of the output derater, for example with electrically
conductive metal cable terminals on a grounded connection rail.
•
Keep the exposed conductor as short as possible. All devices and circuits
that are sensitive to EMC must be kept at a distance of at least 0.3 m.
The graphic below shows an example for the shielded connection of a motor
with output derater (graphic: icotek GmbH).
Pin 7 and
8 are
bridged at
the output
derator
1U1 1U2
1V1 1V2
1W1 1W2
7
PE
8
PE