ID 442426.04
370
WE KEEP THINGS MOVING
Diagnosis
16
Manual SD6
16.5 35:Watchdog
17: opt1 databus
The test of the databus for option 1 returned
errors.
•
Uninstall and reinstall the option.
•
Replace the option.
No
18:Opt2 Adr/Databus
The test of the address/databus for option 2
returned errors.
•
Uninstall and reinstall the option.
•
Replace the option.
No
19: Opt2 signal line
The test of the CAN/Interrupt/Wait line for
option 2 returned errors.
•
Uninstall and reinstall the option.
•
Replace the option.
No
20: opt2 clk fault
The test of the clock signal for option 2
returned errors.
•
Uninstall and reinstall the option.
•
Replace the option.
No
21: opt2 voltage
The test of the required power supply
voltage for option 2 returned errors.
•
Uninstall and reinstall the option.
•
Replace the option.
No
22: opt2 databus
The test of the databus for option 2 returned
errors.
•
Uninstall and reinstall the option.
•
Replace the option.
No
Triggering
Level
Response
Counter
The watchdog of the microprocessor is activated.
Fault
The power board is switched off and the drive becomes
torque-free/force-free. A possibly existing brake will be
controlled to close.
While the runtime system of the drive controller is
restarted, the brake chopper is switched off and the brake
air override has no function.
Z35
Cause
Description
Measure
Confirmable
1:Core 0
The microprocessor is used to capacity or
faulty.
•
Set a higher cycle time in the
A150
parameter.
•
Wire according to EMC regulations.
Yes
2:Core 1
Cause
Description
Measure
Confirmable