ID 442426.04
193
WE KEEP THINGS MOVING
Drive controller
9
Manual SD6
9.5.4
Thermal
The following display parameter provides you with further information:
•
Element 0: Current temperature of the power board/ IGBT in °C.
•
Element 1: Current temperature of the control board in °C.
The lowest measured temperatures are saved in the elements of this
parameter in non-volatile memory.
•
Element 0: Temperature of the power board/IGBT
•
Element 1: Temperature of the control board
These values can be reset with
A37
.
The highest measured temperatures are saved in the elements of this
parameter in non-volatile memory.
•
Element 0: Temperature of the power board/IGBT
•
Element 1: Temperature of the control board
These values can be reset with
A37
.
9.6
Cycle time
The application is processed with the cycle time set in
A150
. If the drive
controller is unable to process the application in the set time because utilization
is too high, fault
57: runtime load
is triggered. A detailed description of the fault
can be found in section 16.27 57:Runtime usage. In this case set
A150
to a
higher value.
The current utilization of the drive controller can be found in parameter
E191
runtime usage
. If the parameter has a value > 75 %, you should set
A150
to a
higher value. Note that
E191
starts at 0 % when you have changed
A150
.
Cycle time of real-time configuration in the axis.
The usage of the real-time task can be checked in parameter
E191 runtime
usage
. If the computing load is too heavy event
57:runtime usage
is triggered.
9.7
Components
The following parameters provide information about which components were
created in your project and which ones are actually present.
Display of the drive controller designation including SafetyModule and options,
for example SD6A06TEX.
Corresponds to object index 1008
hex
subindex 0
hex
Manufacturer device name
in accordance with CiA 301.
Projected drive controller in DriveControlSuite (without options modules), for
example SD6A06.
E25
drive controller temperature
version 0
E35
Tmin-memorized value
version 0
E36
Tmax-memorized value
version 0
A150
cycle time
version 0
E50
drive controller
version 0
E51
required drive controller
version 0
E52
drive controller information
version 0