Diagnosis
16
Manual SD6
16.25 55:Option module
Triggering
Level
Response
Counter
Error when operating with option module.
Fault
Parameterized fault response in
A29
:
•
A29 = 0:inactive
The power board is switched off and the drive
becomes torque-free/force-free. If the air override is
inactive, a possibly existing brake will be controlled to
close.
•
A29 = 1:active
The drive is stopped with a quick stop. If the air
override is inactive, a possibly existing brake will be
controlled to close at the end of the quick stop.
Z55
Cause
Description
Measure
Confirmable
1:incorrectOption1
Incorrect or missing communication module
(compare
E54/E58
with
E68/E69
)
•
Install the projected communication
module.
•
Adjust the projection.
Yes
2:EC6failure
EC6 was detected, installed and failed.
•
Uninstall and reinstall ED6.
•
Replace EC6.
Yes
3:CA6failure
CA6 was detected, installed and failed.
•
Uninstall and reinstall CA6.
•
Replace CA6.
Yes
7:incorrectOption2
Incorrect or missing terminal module
(compare
E54/E58
with
E68/E69
)
•
Install the projected terminal module.
•
Adjust the projection.
Yes
10:XI6failure
X16 was detected, installed and failed.
•
Uninstall and reinstall X16.
•
Adjust the projection.
Yes
12:24Vfailure
A failure of the 24 vdc power supply of XI6
was detected.
Check and, if necessary, correct the 24 vdc
power supply of X16.
Yes