Diagnosis
16
Manual SD6
16.8 38:TempDev.sens
Triggering
Level
Response
Counter
The temperature measured by the device sensor
exceeds the permitted maximum value
R05
or has
fallen below the permitted minimum value
R25
.
The permitted temperatures are saved in the
power stage of the drive controller.
Fault
Parameterized fault response in
A29
:
•
A29 = 0:inactive
The power board is switched off and the drive
becomes torque-free/force-free. If the air override is
inactive, a possibly existing brake will be controlled to
close.
•
A29 = 1:active
The drive is stopped with a quick stop. If the air
override is inactive, a possibly existing brake will be
controlled to close at the end of the quick stop.
Z38
Possible cause
Test
Measure
Confirmable
The ambient/control cabinet
temperatures are too high or too low.
Check the surrounding temperature of the
drive controller.
Take suitable measures to match the
surrounding temperature to the operating
conditions of the drive controller.
Yes
Fan faulty
Switch on the control part power supply and
check whether the fan(s) start up.
Please contact our Service department.