![Stober SD6 Series Скачать руководство пользователя страница 34](http://html.mh-extra.com/html/stober/sd6-series/sd6-series_manual_1381243034.webp)
ID 442426.04
34
WE KEEP THINGS MOVING
Technical data
4
Manual SD6
4.4
Transportation, storage and operating
environment
NOTICE
Material damage!
The DC link capacitors in devices of sizes 0, 1 and 2 can lose their electrical
strength through long storage times. Considerable material damage can arise
from a reduced electrical strength of the DC link capacitors when switching on.
Use devices in storage annually or before startup.
Surrounding operating
temperature
0 °C to 45 °C for nominal data
Storage/
transport temperature
-20 °C to +70 °C
Maximum change: 20 K/h
Relative humidity
Maximum relative humidity 85 %, non-
condensing
Installation altitude
Up to 1000 m above sea level without restrictions
Pollution degree
Pollution degree level 2 as per EN 50178
Ventilated
Installed fan
Vibration (operation)
5 Hz
≤
f
≤
9 Hz: 0.35 mm
9 Hz
≤
f
≤
200 Hz: 1 m/s
2
Vibration (transport)
5 Hz
≤
f
≤
9 Hz: 3.5 mm
9 Hz
≤
f
≤
200 Hz: 10 m/s
2
200 Hz
≤
f
≤
500 Hz: 15 m/s
2