8.2
Modulating output (AO)
8.2.1
Purpose and activation
The AO x (modulating output) function block generates a continuous DC 0…10 V
output signal for a modulating actuator with a corresponding input.
Purpose of AO x
The AO x function block is not available with the RLU220 controller.
Note
To activate the AO x function block, you must assign an output (Y x) to it.
Activation
8.2.2
Function
You can connect the load signal for the modulating output from the sequence
controller to the modulating output.
External signal (IN X)
Additionally, it is also possible to use an analog input (IN X) as the load signal. If
one or more (maximum 2) internal load signals and the external load signal are
connected at the same time, the controller uses maximum selection.
For example, this provides for combination of the air cooling coil signal from an
external dehumidification controller with that from a temperature controller.
The external signal is considered only if the controller operates in Comfort or
Economy mode!
Note
You can invert any output. Meaning:
Output inversion
(INVERS)
INVERS = NO: 0…100% load = 0…100% output
INVERS = YES: 0…100% load = 100…0% output
If the controller has an analog output and is switched off during operation (input D1
= Protection), the output signal behaves as follows:
INVERS = NO: 0% output
INVERS = YES: 100% output
59 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Aggregates
29.08.2008