7.7
Room temperature (ROOM)
7.7.1
Activation and functionality
You can activate the function by setting identifier
ROOM
(outside temperature) at
the respective input.
Activating the function
ROOM (outside temperature) is a special identifier because it creates automatically
a large number of “internal connections”. ROOM can only be selected in basic type
A.
The other properties, such as measuring range, troubleshooting, etc., are
described in chapter 0 "Analog inputs".
Additional functionality
7.7.2
Settings
Path:
… > COMMIS > CONF > X1
Configuration
… > COMMIS > CONF > X5
Display
Name
Range / comments
LABEL Input
identifier
ROOM
Path:
… > PARA > X1…X5
Setting values
Display
Name
Range
Factory setting
TYPE
Type
NI, 2XNI, T1, PT, 0-10
NI
MIN VAL
Value low
−
50…
+
500 -50
MAX VAL
Value high
−
50…
+
500 250
CORR Correction
−
3.0…
+
3.0 0
K
Path:
INFO
Display values
Display
Name
Comments
ROOM Room
temperature
Path:
… > COMMIS > TEST
Wiring test
Display
Name
Positions
ROOM
Room temperature
Indication of room temperature (at terminal
Xx and as display value ROOM), non-
adjustable
Display
Name
Effect
Xx --- / ooo
Sensor error X…
Non-urgent message; plant not stopped
Fault status messages
52 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Inputs
29.08.2008