9.8.3
Troubleshooting
If there is no outside temperature sensor signal, the controller does not disable the
sequences.
OT sensor signal
available?
9.8.4
Settings
Path:
… > PARA > CTLOOP 1
Setting values
… > PARA > CTLOOP 2
Display
Name
Range
Factory
setting
LOCK S1
[Sequence 1] outside temp >
−
50…
+
250 °C 250 °C
LOCK S2
[Sequence 2] outside temp >
−
50…
+
250 °C 250 °C
LOCK S4
[Sequence 4] outside temp <
−
50…
+
250 °C
−
50 °C
LOCK S5
[Sequence 5] outside temp <
−
50…
+
250 °C
−
50 °C
9.8.5
Application example
Disabling a preheater on sequence 2 at temperatures above 10 °C.
Preheater
Function: Valve fully closed, pump off.
128 / 174
Siemens
Universal Controllers RLU2…
CE1P3101en
Building Technologies
Controller (CTLOOP x)
29.08.2008