Example with 2 digital outputs:
Switching interval
0 %
a
a
a
a
a
a
0 %
AO
¼ a
31
01
D
19
Q
0Y + 2Q
S2-ON
S1-ON
S2-OFF
S1-OFF
1Y + 2Q
Q
MAX POS
MIN POS
100 %
100 %
STEP 1
STEP 2
1)
steps
of
(number
load
%
100
a
Interval
+
=
Additionally, you can enter a common locking time for the relay outputs. This
ensures that a step that has just switched off remains off for at least the set period
of time.
Locking time
(OFFTIME)
To prevent excessively quick startup, you can enter a common startup delay time.
This delay makes the controller wait for the set time between the steps during
startup.
Startup delay
(ON DLY)
With the linear step switch, you can set a priority changeover of the outputs.
Run time priority
changeover (PRIO CH)
The priorities change at fixed intervals of roughly one week (always after 7 x 24 =
168 hours).
Changeover is as follows (example with 4 steps):
Week 1: 1, 2, 3, 4
Week 2: 2, 3, 4, 1
Week 3: 3, 4, 1, 2
Week 4: 4, 1, 2, 3
Week 5: 1, 2, 3, 4
Etc.
In the event of a voltage drop, priority changeover is reset.
Note
81 / 174